Violation history (56)

SeverityDateStandard / narrativeCorrected
? 470 IAC 3-4.7-114(d) — The center shall use an antiscald valve approved by ISDH to maintain water temperature between one hundred (100) degrees Fahrenheit and one hundred twenty (120) degrees Fahrenheit on all hot water supplied to sinks, bathing, and washing facilities used by children.
The Loss Control Inspector for the Harford Steam Boiler turned off the Antiscald valve during visit as it is broken. Making it no longer in use.
Yes
? 470 IAC 3-4.7-114(c) — The center shall provide hot and cold running water at all hand washing sinks
Room 301 has a temperatuer of 121.6 degrees F at the handwashing sink. Rooms 201 and 202 did not have hot water at the hand washing sink.
Yes
? 470 IAC 3-4.7-100(e) — The center must store cleaning equipment, cleaning agents, aerosol cans, and any other item that states keep out of the reach of children in a place that is inaccessible to children
There are clorox wipes and a first aid kit labeled keep out of reach of children on the white table in the indoor play area.
Yes
? 470 IAC 3-4.7-113 — Bathrooms
Room 304 has balls, an easel, push toys and a play vaccum stored stored. Items in bathrooms should be used for toileting.
Yes
? 410 IAC 7-24-330 — Water pressure
Room 203 has minimal water pressure in the children's handwashing sink.
Yes
? 410 IAC 7-24-330 — Water pressure
Room 203 has minimal water pressure in the children's handwashing sink.
Yes
? 470 IAC 3-4.7-136 — Breast Milk
The crock pot in the infant kitchen is reading 147 degrees F. The temperature should be between 100 and 120.
Yes
? 470 IAC 3-4.5-6(d) — Diapers. The diapering process shall be done on a table, in a clean and sanitary manner. The diaper changing surface shall be sanitized after each use and materials used for skin cleansing shall be discarded after each use into a tightly covered, easily sanitized container. Individuals responsible for diaper changing shall wash their hands after each diaper change
Room 306 has dirt around and under the diaper changing pad.
Yes
? 470 IAC 3-4.7-114(c) — The center shall provide hot and cold running water at all hand washing sinks
Room 301 has a temperatuer of 121.6 degrees F at the handwashing sink. Rooms 201 and 202 did not have hot water at the hand washing sink.
Yes
? 470 IAC 3-4.7-114(d) — The center shall use an antiscald valve approved by ISDH to maintain water temperature between one hundred (100) degrees Fahrenheit and one hundred twenty (120) degrees Fahrenheit on all hot water supplied to sinks, bathing, and washing facilities used by children.
The Loss Control Inspector for the Harford Steam Boiler turned off the Antiscald valve during visit as it is broken. Making it no longer in use.
Yes
? 470 IAC 3-4.7-100(e) — The center must store cleaning equipment, cleaning agents, aerosol cans, and any other item that states keep out of the reach of children in a place that is inaccessible to children
There are clorox wipes and a first aid kit labeled keep out of reach of children on the white table in the indoor play area.
Yes
? 470 IAC 3-4.7-113 — Bathrooms
Room 304 has balls, an easel, push toys and a play vaccum stored stored. Items in bathrooms should be used for toileting.
Yes
? 410 IAC 7-24-330 — Water pressure
Room 203 has minimal water pressure in the children's handwashing sink.
Yes
? 410 IAC 7-24-330 — Water pressure
Room 203 has minimal water pressure in the children's handwashing sink.
Yes
? 470 IAC 3-4.7-136 — Breast Milk
The crock pot in the infant kitchen is reading 147 degrees F. The temperature should be between 100 and 120.
Yes
? 470 IAC 3-4.5-6(d) — Diapers. The diapering process shall be done on a table, in a clean and sanitary manner. The diaper changing surface shall be sanitized after each use and materials used for skin cleansing shall be discarded after each use into a tightly covered, easily sanitized container. Individuals responsible for diaper changing shall wash their hands after each diaper change
Room 306 has dirt around and under the diaper changing pad.
Yes
? 470 IAC 3-4.7-114(d) — The center shall use an antiscald valve approved by ISDH to maintain water temperature between one hundred (100) degrees Fahrenheit and one hundred twenty (120) degrees Fahrenheit on all hot water supplied to sinks, bathing, and washing facilities used by children.
The Loss Control Inspector for the Harford Steam Boiler turned off the Antiscald valve during visit as it is broken. Making it no longer in use.
Yes
? 470 IAC 3-4.7-114(c) — The center shall provide hot and cold running water at all hand washing sinks
Room 301 has a temperatuer of 121.6 degrees F at the handwashing sink. Rooms 201 and 202 did not have hot water at the hand washing sink.
Yes
? 410 IAC 7-24-330 — Water pressure
Room 203 has minimal water pressure in the children's handwashing sink.
Yes
? 410 IAC 7-24-330 — Water pressure
Room 203 has minimal water pressure in the children's handwashing sink.
Yes
? 470 IAC 3-4.7-100(e) — The center must store cleaning equipment, cleaning agents, aerosol cans, and any other item that states keep out of the reach of children in a place that is inaccessible to children
There are clorox wipes and a first aid kit labeled keep out of reach of children on the white table in the indoor play area.
Yes
? 470 IAC 3-4.7-113 — Bathrooms
Room 304 has balls, an easel, push toys and a play vaccum stored stored. Items in bathrooms should be used for toileting.
Yes
? 470 IAC 3-4.5-6(d) — Diapers. The diapering process shall be done on a table, in a clean and sanitary manner. The diaper changing surface shall be sanitized after each use and materials used for skin cleansing shall be discarded after each use into a tightly covered, easily sanitized container. Individuals responsible for diaper changing shall wash their hands after each diaper change
Room 306 has dirt around and under the diaper changing pad.
Yes
? 470 IAC 3-4.7-136 — Breast Milk
The crock pot in the infant kitchen is reading 147 degrees F. The temperature should be between 100 and 120.
Yes
? 470 IAC 3-4.7-114(d) — The center shall use an antiscald valve approved by ISDH to maintain water temperature between one hundred (100) degrees Fahrenheit and one hundred twenty (120) degrees Fahrenheit on all hot water supplied to sinks, bathing, and washing facilities used by children.
The Loss Control Inspector for the Harford Steam Boiler turned off the Antiscald valve during visit as it is broken. Making it no longer in use.
Yes
? 470 IAC 3-4.7-114(c) — The center shall provide hot and cold running water at all hand washing sinks
Room 301 has a temperatuer of 121.6 degrees F at the handwashing sink. Rooms 201 and 202 did not have hot water at the hand washing sink.
Yes
? 470 IAC 3-4.5-6(d) — Diapers. The diapering process shall be done on a table, in a clean and sanitary manner. The diaper changing surface shall be sanitized after each use and materials used for skin cleansing shall be discarded after each use into a tightly covered, easily sanitized container. Individuals responsible for diaper changing shall wash their hands after each diaper change
Room 306 has dirt around and under the diaper changing pad.
Yes
? 410 IAC 7-24-330 — Water pressure
Room 203 has minimal water pressure in the children's handwashing sink.
Yes
? 410 IAC 7-24-330 — Water pressure
Room 203 has minimal water pressure in the children's handwashing sink.
Yes
? 470 IAC 3-4.7-100(e) — The center must store cleaning equipment, cleaning agents, aerosol cans, and any other item that states keep out of the reach of children in a place that is inaccessible to children
There are clorox wipes and a first aid kit labeled keep out of reach of children on the white table in the indoor play area.
Yes
? 470 IAC 3-4.7-113 — Bathrooms
Room 304 has balls, an easel, push toys and a play vaccum stored stored. Items in bathrooms should be used for toileting.
Yes
? 470 IAC 3-4.7-136 — Breast Milk
The crock pot in the infant kitchen is reading 147 degrees F. The temperature should be between 100 and 120.
Yes
? 470 IAC 3-4.7-114(d) — The center shall use an antiscald valve approved by ISDH to maintain water temperature between one hundred (100) degrees Fahrenheit and one hundred twenty (120) degrees Fahrenheit on all hot water supplied to sinks, bathing, and washing facilities used by children.
The Loss Control Inspector for the Harford Steam Boiler turned off the Antiscald valve during visit as it is broken. Making it no longer in use.
Yes
? 470 IAC 3-4.7-114(c) — The center shall provide hot and cold running water at all hand washing sinks
Room 301 has a temperatuer of 121.6 degrees F at the handwashing sink. Rooms 201 and 202 did not have hot water at the hand washing sink.
Yes
? 410 IAC 7-24-330 — Water pressure
Room 203 has minimal water pressure in the children's handwashing sink.
Yes
? 410 IAC 7-24-330 — Water pressure
Room 203 has minimal water pressure in the children's handwashing sink.
Yes
? 470 IAC 3-4.7-100(e) — The center must store cleaning equipment, cleaning agents, aerosol cans, and any other item that states keep out of the reach of children in a place that is inaccessible to children
There are clorox wipes and a first aid kit labeled keep out of reach of children on the white table in the indoor play area.
Yes
? 470 IAC 3-4.7-113 — Bathrooms
Room 304 has balls, an easel, push toys and a play vaccum stored stored. Items in bathrooms should be used for toileting.
Yes
? 470 IAC 3-4.7-136 — Breast Milk
The crock pot in the infant kitchen is reading 147 degrees F. The temperature should be between 100 and 120.
Yes
? 470 IAC 3-4.5-6(d) — Diapers. The diapering process shall be done on a table, in a clean and sanitary manner. The diaper changing surface shall be sanitized after each use and materials used for skin cleansing shall be discarded after each use into a tightly covered, easily sanitized container. Individuals responsible for diaper changing shall wash their hands after each diaper change
Room 306 has dirt around and under the diaper changing pad.
Yes
? 470 IAC 3-4.7-114(d) — The center shall use an antiscald valve approved by ISDH to maintain water temperature between one hundred (100) degrees Fahrenheit and one hundred twenty (120) degrees Fahrenheit on all hot water supplied to sinks, bathing, and washing facilities used by children.
The Loss Control Inspector for the Harford Steam Boiler turned off the Antiscald valve during visit as it is broken. Making it no longer in use.
Yes
? 470 IAC 3-4.7-114(c) — The center shall provide hot and cold running water at all hand washing sinks
Room 301 has a temperatuer of 121.6 degrees F at the handwashing sink. Rooms 201 and 202 did not have hot water at the hand washing sink.
Yes
? 470 IAC 3-4.7-100(e) — The center must store cleaning equipment, cleaning agents, aerosol cans, and any other item that states keep out of the reach of children in a place that is inaccessible to children
There are clorox wipes and a first aid kit labeled keep out of reach of children on the white table in the indoor play area.
Yes
? 470 IAC 3-4.7-113 — Bathrooms
Room 304 has balls, an easel, push toys and a play vaccum stored stored. Items in bathrooms should be used for toileting.
Yes
? 410 IAC 7-24-330 — Water pressure
Room 203 has minimal water pressure in the children's handwashing sink.
Yes
? 410 IAC 7-24-330 — Water pressure
Room 203 has minimal water pressure in the children's handwashing sink.
Yes
? 470 IAC 3-4.7-136 — Breast Milk
The crock pot in the infant kitchen is reading 147 degrees F. The temperature should be between 100 and 120.
Yes
? 470 IAC 3-4.5-6(d) — Diapers. The diapering process shall be done on a table, in a clean and sanitary manner. The diaper changing surface shall be sanitized after each use and materials used for skin cleansing shall be discarded after each use into a tightly covered, easily sanitized container. Individuals responsible for diaper changing shall wash their hands after each diaper change
Room 306 has dirt around and under the diaper changing pad.
Yes
? 470 IAC 3-4.7-114(c) — The center shall provide hot and cold running water at all hand washing sinks
Room 301 has a temperatuer of 121.6 degrees F at the handwashing sink. Rooms 201 and 202 did not have hot water at the hand washing sink.
Yes
? 470 IAC 3-4.7-114(d) — The center shall use an antiscald valve approved by ISDH to maintain water temperature between one hundred (100) degrees Fahrenheit and one hundred twenty (120) degrees Fahrenheit on all hot water supplied to sinks, bathing, and washing facilities used by children.
The Loss Control Inspector for the Harford Steam Boiler turned off the Antiscald valve during visit as it is broken. Making it no longer in use.
Yes
? 470 IAC 3-4.7-100(e) — The center must store cleaning equipment, cleaning agents, aerosol cans, and any other item that states keep out of the reach of children in a place that is inaccessible to children
There are clorox wipes and a first aid kit labeled keep out of reach of children on the white table in the indoor play area.
Yes
? 470 IAC 3-4.7-113 — Bathrooms
Room 304 has balls, an easel, push toys and a play vaccum stored stored. Items in bathrooms should be used for toileting.
Yes
? 410 IAC 7-24-330 — Water pressure
Room 203 has minimal water pressure in the children's handwashing sink.
Yes
? 410 IAC 7-24-330 — Water pressure
Room 203 has minimal water pressure in the children's handwashing sink.
Yes
? 470 IAC 3-4.7-136 — Breast Milk
The crock pot in the infant kitchen is reading 147 degrees F. The temperature should be between 100 and 120.
Yes
? 470 IAC 3-4.5-6(d) — Diapers. The diapering process shall be done on a table, in a clean and sanitary manner. The diaper changing surface shall be sanitized after each use and materials used for skin cleansing shall be discarded after each use into a tightly covered, easily sanitized container. Individuals responsible for diaper changing shall wash their hands after each diaper change
Room 306 has dirt around and under the diaper changing pad.
Yes

Severity 5 = most serious. Source: official state record.

Inspections (84)

84 inspection record(s) on file from IN-FSSA.

Ownership

Amanda Peters

Nearby alternatives

FacilityScoreCityDistance
G&K Sunshine Sprouts Childcare LLC 100 1.4 km
Carver Community Organization 58 Evansville1.4 km
A Child's Paradise 58 Evansville1.5 km
Delaware Ed Center 16 Evansville1.3 km
Deaconess Children's Enrichment Center 0 Evansville0.4 km
St Vincent Early Learning Center, Inc 0 Evansville0.5 km

Licensed facilities near this one, highest compliance score first.

Get violation alerts for this daycare

We'll email you when a new inspection or violation is posted. Free.