Indiana › Here We Grow Daycare & Learning Center

Here We Grow Daycare & Learning Center

Family child care home · , IN 46628 · License 812426

0Compliance score
Poor

Capacity 12. Infant

Violation history (49)

SeverityDateStandard / narrativeCorrected
? 470 IAC 3-1.1-46(q) — The licensee shall identify the location and operation of the gas, electric, and water shut-offs and keep accessible the gas, electric, and water shut-offs in case of emergency.
The provider did not have the gas, electric or water marked with shut off tags.
Yes
? 470 IAC 3-1.1-45(a) — The licensee shall ensure that no conditions exist in the home or on the grounds where child care services are provided that would endanger the health, safety, or welfare of the children
Front deck area is missing planks and has exposed nails. Back deck also has missing planks and exposed nails. There is building debri on the playground area that needs to be removed. The underpart of the decks that are large do not have covering where the children have access to under the house. Lattice work has been started and needs to be completed. There is a opening to the basement on the playground that is deep and needs to be covered and secured.
Yes
4 470 IAC 3-1.1-46(l) — Licensee shall provide electrical or battery-operated smoke detector that is installed to manufacturers specifications and is located and adjusted to operate reliably in case of smoke in any part of the child care home, including not less than one (1) smoke detector at the top of each stairway and adjacent to all sleeping areas. The alarm should be loud enough to alert all occupants in the child care home
The provider needs a smoke detector at the top of the basement stairs.
Yes
4 470 IAC 3-1.1-45(d) — The licensee shall provide a protected outdoor play area that is safely enclosed by either a fence or natural boundaries for children in care
There are missing panels on the fence that need to be repaired and the side gate nees o be secured.
Yes
? 470 IAC 3-1.1-48(a) — Direct child care providers shall keep protective coverings over exposed electrical outlets
The provider did not have any of the outlets covered with protecters.
Yes
? 470 IAC 3-1.1-47(d) — Caregiver shall keep garbage in containers with tight-fitting lids and remove it from the premises at least once a week. Waste paper need not be kept in a closed container
The provider does not have a garbage can in the kitchen that has a tight fitting lid.
Yes
? 470 IAC 3-1.1-46(m) — Licensee shall provide a two and one-half (2) pound or greater ABC multiple purpose fire extinguisher which shall be located on each floor of the building in which child care services are provided, including an additional extinguisher located in the kitchen area of the child care home
The provider needs a fire extinguisher in the lithcne, the main area and the basement of the daycare.
Yes
? 470 IAC 3-1.1-47(d) — Caregiver shall keep garbage in containers with tight-fitting lids and remove it from the premises at least once a week. Waste paper need not be kept in a closed container
The provider does not have a garbage can in the kitchen that has a tight fitting lid.
Yes
? 470 IAC 3-1.1-46(q) — The licensee shall identify the location and operation of the gas, electric, and water shut-offs and keep accessible the gas, electric, and water shut-offs in case of emergency.
The provider did not have the gas, electric or water marked with shut off tags.
Yes
? 470 IAC 3-1.1-45(a) — The licensee shall ensure that no conditions exist in the home or on the grounds where child care services are provided that would endanger the health, safety, or welfare of the children
Front deck area is missing planks and has exposed nails. Back deck also has missing planks and exposed nails. There is building debri on the playground area that needs to be removed. The underpart of the decks that are large do not have covering where the children have access to under the house. Lattice work has been started and needs to be completed. There is a opening to the basement on the playground that is deep and needs to be covered and secured.
Yes
4 470 IAC 3-1.1-46(l) — Licensee shall provide electrical or battery-operated smoke detector that is installed to manufacturers specifications and is located and adjusted to operate reliably in case of smoke in any part of the child care home, including not less than one (1) smoke detector at the top of each stairway and adjacent to all sleeping areas. The alarm should be loud enough to alert all occupants in the child care home
The provider needs a smoke detector at the top of the basement stairs.
Yes
4 470 IAC 3-1.1-45(d) — The licensee shall provide a protected outdoor play area that is safely enclosed by either a fence or natural boundaries for children in care
There are missing panels on the fence that need to be repaired and the side gate nees o be secured.
Yes
? 470 IAC 3-1.1-48(a) — Direct child care providers shall keep protective coverings over exposed electrical outlets
The provider did not have any of the outlets covered with protecters.
Yes
? 470 IAC 3-1.1-46(m) — Licensee shall provide a two and one-half (2) pound or greater ABC multiple purpose fire extinguisher which shall be located on each floor of the building in which child care services are provided, including an additional extinguisher located in the kitchen area of the child care home
The provider needs a fire extinguisher in the lithcne, the main area and the basement of the daycare.
Yes
? 470 IAC 3-1.1-46(q) — The licensee shall identify the location and operation of the gas, electric, and water shut-offs and keep accessible the gas, electric, and water shut-offs in case of emergency.
The provider did not have the gas, electric or water marked with shut off tags.
Yes
? 470 IAC 3-1.1-45(a) — The licensee shall ensure that no conditions exist in the home or on the grounds where child care services are provided that would endanger the health, safety, or welfare of the children
Front deck area is missing planks and has exposed nails. Back deck also has missing planks and exposed nails. There is building debri on the playground area that needs to be removed. The underpart of the decks that are large do not have covering where the children have access to under the house. Lattice work has been started and needs to be completed. There is a opening to the basement on the playground that is deep and needs to be covered and secured.
Yes
4 470 IAC 3-1.1-46(l) — Licensee shall provide electrical or battery-operated smoke detector that is installed to manufacturers specifications and is located and adjusted to operate reliably in case of smoke in any part of the child care home, including not less than one (1) smoke detector at the top of each stairway and adjacent to all sleeping areas. The alarm should be loud enough to alert all occupants in the child care home
The provider needs a smoke detector at the top of the basement stairs.
Yes
4 470 IAC 3-1.1-45(d) — The licensee shall provide a protected outdoor play area that is safely enclosed by either a fence or natural boundaries for children in care
There are missing panels on the fence that need to be repaired and the side gate nees o be secured.
Yes
? 470 IAC 3-1.1-48(a) — Direct child care providers shall keep protective coverings over exposed electrical outlets
The provider did not have any of the outlets covered with protecters.
Yes
? 470 IAC 3-1.1-47(d) — Caregiver shall keep garbage in containers with tight-fitting lids and remove it from the premises at least once a week. Waste paper need not be kept in a closed container
The provider does not have a garbage can in the kitchen that has a tight fitting lid.
Yes
? 470 IAC 3-1.1-46(m) — Licensee shall provide a two and one-half (2) pound or greater ABC multiple purpose fire extinguisher which shall be located on each floor of the building in which child care services are provided, including an additional extinguisher located in the kitchen area of the child care home
The provider needs a fire extinguisher in the lithcne, the main area and the basement of the daycare.
Yes
? 470 IAC 3-1.1-47(d) — Caregiver shall keep garbage in containers with tight-fitting lids and remove it from the premises at least once a week. Waste paper need not be kept in a closed container
The provider does not have a garbage can in the kitchen that has a tight fitting lid.
Yes
? 470 IAC 3-1.1-46(m) — Licensee shall provide a two and one-half (2) pound or greater ABC multiple purpose fire extinguisher which shall be located on each floor of the building in which child care services are provided, including an additional extinguisher located in the kitchen area of the child care home
The provider needs a fire extinguisher in the lithcne, the main area and the basement of the daycare.
Yes
? 470 IAC 3-1.1-46(q) — The licensee shall identify the location and operation of the gas, electric, and water shut-offs and keep accessible the gas, electric, and water shut-offs in case of emergency.
The provider did not have the gas, electric or water marked with shut off tags.
Yes
? 470 IAC 3-1.1-45(a) — The licensee shall ensure that no conditions exist in the home or on the grounds where child care services are provided that would endanger the health, safety, or welfare of the children
Front deck area is missing planks and has exposed nails. Back deck also has missing planks and exposed nails. There is building debri on the playground area that needs to be removed. The underpart of the decks that are large do not have covering where the children have access to under the house. Lattice work has been started and needs to be completed. There is a opening to the basement on the playground that is deep and needs to be covered and secured.
Yes
4 470 IAC 3-1.1-46(l) — Licensee shall provide electrical or battery-operated smoke detector that is installed to manufacturers specifications and is located and adjusted to operate reliably in case of smoke in any part of the child care home, including not less than one (1) smoke detector at the top of each stairway and adjacent to all sleeping areas. The alarm should be loud enough to alert all occupants in the child care home
The provider needs a smoke detector at the top of the basement stairs.
Yes
4 470 IAC 3-1.1-45(d) — The licensee shall provide a protected outdoor play area that is safely enclosed by either a fence or natural boundaries for children in care
There are missing panels on the fence that need to be repaired and the side gate nees o be secured.
Yes
? 470 IAC 3-1.1-48(a) — Direct child care providers shall keep protective coverings over exposed electrical outlets
The provider did not have any of the outlets covered with protecters.
Yes
? 470 IAC 3-1.1-46(q) — The licensee shall identify the location and operation of the gas, electric, and water shut-offs and keep accessible the gas, electric, and water shut-offs in case of emergency.
The provider did not have the gas, electric or water marked with shut off tags.
Yes
? 470 IAC 3-1.1-45(a) — The licensee shall ensure that no conditions exist in the home or on the grounds where child care services are provided that would endanger the health, safety, or welfare of the children
Front deck area is missing planks and has exposed nails. Back deck also has missing planks and exposed nails. There is building debri on the playground area that needs to be removed. The underpart of the decks that are large do not have covering where the children have access to under the house. Lattice work has been started and needs to be completed. There is a opening to the basement on the playground that is deep and needs to be covered and secured.
Yes
4 470 IAC 3-1.1-46(l) — Licensee shall provide electrical or battery-operated smoke detector that is installed to manufacturers specifications and is located and adjusted to operate reliably in case of smoke in any part of the child care home, including not less than one (1) smoke detector at the top of each stairway and adjacent to all sleeping areas. The alarm should be loud enough to alert all occupants in the child care home
The provider needs a smoke detector at the top of the basement stairs.
Yes
4 470 IAC 3-1.1-45(d) — The licensee shall provide a protected outdoor play area that is safely enclosed by either a fence or natural boundaries for children in care
There are missing panels on the fence that need to be repaired and the side gate nees o be secured.
Yes
? 470 IAC 3-1.1-48(a) — Direct child care providers shall keep protective coverings over exposed electrical outlets
The provider did not have any of the outlets covered with protecters.
Yes
? 470 IAC 3-1.1-47(d) — Caregiver shall keep garbage in containers with tight-fitting lids and remove it from the premises at least once a week. Waste paper need not be kept in a closed container
The provider does not have a garbage can in the kitchen that has a tight fitting lid.
Yes
? 470 IAC 3-1.1-46(m) — Licensee shall provide a two and one-half (2) pound or greater ABC multiple purpose fire extinguisher which shall be located on each floor of the building in which child care services are provided, including an additional extinguisher located in the kitchen area of the child care home
The provider needs a fire extinguisher in the lithcne, the main area and the basement of the daycare.
Yes
? 470 IAC 3-1.1-46(q) — The licensee shall identify the location and operation of the gas, electric, and water shut-offs and keep accessible the gas, electric, and water shut-offs in case of emergency.
The provider did not have the gas, electric or water marked with shut off tags.
Yes
? 470 IAC 3-1.1-45(a) — The licensee shall ensure that no conditions exist in the home or on the grounds where child care services are provided that would endanger the health, safety, or welfare of the children
Front deck area is missing planks and has exposed nails. Back deck also has missing planks and exposed nails. There is building debri on the playground area that needs to be removed. The underpart of the decks that are large do not have covering where the children have access to under the house. Lattice work has been started and needs to be completed. There is a opening to the basement on the playground that is deep and needs to be covered and secured.
Yes
4 470 IAC 3-1.1-46(l) — Licensee shall provide electrical or battery-operated smoke detector that is installed to manufacturers specifications and is located and adjusted to operate reliably in case of smoke in any part of the child care home, including not less than one (1) smoke detector at the top of each stairway and adjacent to all sleeping areas. The alarm should be loud enough to alert all occupants in the child care home
The provider needs a smoke detector at the top of the basement stairs.
Yes
4 470 IAC 3-1.1-45(d) — The licensee shall provide a protected outdoor play area that is safely enclosed by either a fence or natural boundaries for children in care
There are missing panels on the fence that need to be repaired and the side gate nees o be secured.
Yes
? 470 IAC 3-1.1-48(a) — Direct child care providers shall keep protective coverings over exposed electrical outlets
The provider did not have any of the outlets covered with protecters.
Yes
? 470 IAC 3-1.1-47(d) — Caregiver shall keep garbage in containers with tight-fitting lids and remove it from the premises at least once a week. Waste paper need not be kept in a closed container
The provider does not have a garbage can in the kitchen that has a tight fitting lid.
Yes
? 470 IAC 3-1.1-46(m) — Licensee shall provide a two and one-half (2) pound or greater ABC multiple purpose fire extinguisher which shall be located on each floor of the building in which child care services are provided, including an additional extinguisher located in the kitchen area of the child care home
The provider needs a fire extinguisher in the lithcne, the main area and the basement of the daycare.
Yes
? 470 IAC 3-1.1-48(a) — Direct child care providers shall keep protective coverings over exposed electrical outlets
The provider did not have any of the outlets covered with protecters.
Yes
4 470 IAC 3-1.1-45(d) — The licensee shall provide a protected outdoor play area that is safely enclosed by either a fence or natural boundaries for children in care
There are missing panels on the fence that need to be repaired and the side gate nees o be secured.
Yes
? 470 IAC 3-1.1-46(q) — The licensee shall identify the location and operation of the gas, electric, and water shut-offs and keep accessible the gas, electric, and water shut-offs in case of emergency.
The provider did not have the gas, electric or water marked with shut off tags.
Yes
? 470 IAC 3-1.1-45(a) — The licensee shall ensure that no conditions exist in the home or on the grounds where child care services are provided that would endanger the health, safety, or welfare of the children
Front deck area is missing planks and has exposed nails. Back deck also has missing planks and exposed nails. There is building debri on the playground area that needs to be removed. The underpart of the decks that are large do not have covering where the children have access to under the house. Lattice work has been started and needs to be completed. There is a opening to the basement on the playground that is deep and needs to be covered and secured.
Yes
4 470 IAC 3-1.1-46(l) — Licensee shall provide electrical or battery-operated smoke detector that is installed to manufacturers specifications and is located and adjusted to operate reliably in case of smoke in any part of the child care home, including not less than one (1) smoke detector at the top of each stairway and adjacent to all sleeping areas. The alarm should be loud enough to alert all occupants in the child care home
The provider needs a smoke detector at the top of the basement stairs.
Yes
? 470 IAC 3-1.1-47(d) — Caregiver shall keep garbage in containers with tight-fitting lids and remove it from the premises at least once a week. Waste paper need not be kept in a closed container
The provider does not have a garbage can in the kitchen that has a tight fitting lid.
Yes
? 470 IAC 3-1.1-46(m) — Licensee shall provide a two and one-half (2) pound or greater ABC multiple purpose fire extinguisher which shall be located on each floor of the building in which child care services are provided, including an additional extinguisher located in the kitchen area of the child care home
The provider needs a fire extinguisher in the lithcne, the main area and the basement of the daycare.
Yes

Severity 5 = most serious. Source: official state record.

Inspections (91)

91 inspection record(s) on file from IN-FSSA.

Ownership

Alice White

Nearby alternatives

FacilityScoreCityDistance
Edwina Smith 100 1.1 km
PASITOS CHILDCARE 100 1.1 km
FUN WORLD CHILDCARE 100 0.8 km
Renee's Forever Learning Childcare 58 0 km
THREE BEARS DAY CARE HOME 58 1.1 km
Open Arms of Love Daycare 58 1.1 km