Violation history (72)

SeverityDateStandard / narrativeCorrected
3 746.1309(a) - Documented Annual Training Area - 24 Hours Required
One caregiver did not have the required 24 hours of training.
4 746.5205(1) - Fire Drill Monthly - Exit in 3 Minutes
The fire drill for November 2022 was not completed. This was corrected at inspection when the director conducted a fire drill.
Yes
5 746.5319 - Smoke Detectors Testing
The operation did not do any monthly testing for the smoke detector this year. This was corrected at inspection when the director tested the smoke detector.
Yes
5 746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months
There was no current fire inspection report available to review during the inspection.
4 746.2419(6) - Requirements for Feeding Infants - Label Bottles/Cups
There were 2 bottles in the infant fridge that were not labeled with the infants name to designate who they belonged too. This was corrected at inspection when the director labeled the bottled in the fridge with the infants name.
Yes
3 745.651(2)(A) - Background Check Validation ? Every 3 months each operation, other than a licensed, registered, or listed home, must validate current list
Employee validation has not been completed since 4.21.2022.
4 746.5537(a)(2) - Electronic or Battery-Operated Carbon Monoxide Detector-Check All Detectors Monthly
The operation did not do any monthly testing for the carbon monoxide this year. This was corrected at inspection when the director tested the carbon monoxide detector.
Yes
3 746.2409(a)(10) - Safety Requirements for Cribs - Label for Each Infant
The cribs in the infant room were labeled with number but did not have a crib chart to associate who the crib belonged to. This was corrected at inspection when the director labeled each crib with the infants information.
Yes
4 746.1315(a) - Each Caregiver and the Director Must Have Current Training in pediatric first aid with rescue breathing and choking.
Four caregiver to include the director did not have a first aid certification.
4 746.5205(1) - Fire Drill Monthly - Exit in 3 Minutes
The fire drill for November 2022 was not completed. This was corrected at inspection when the director conducted a fire drill.
Yes
5 746.5319 - Smoke Detectors Testing
The operation did not do any monthly testing for the smoke detector this year. This was corrected at inspection when the director tested the smoke detector.
Yes
3 745.651(2)(A) - Background Check Validation ? Every 3 months each operation, other than a licensed, registered, or listed home, must validate current list
Employee validation has not been completed since 4.21.2022.
4 746.5537(a)(2) - Electronic or Battery-Operated Carbon Monoxide Detector-Check All Detectors Monthly
The operation did not do any monthly testing for the carbon monoxide this year. This was corrected at inspection when the director tested the carbon monoxide detector.
Yes
4 746.1315(a) - Each Caregiver and the Director Must Have Current Training in pediatric first aid with rescue breathing and choking.
Four caregiver to include the director did not have a first aid certification.
5 746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months
There was no current fire inspection report available to review during the inspection.
4 746.2419(6) - Requirements for Feeding Infants - Label Bottles/Cups
There were 2 bottles in the infant fridge that were not labeled with the infants name to designate who they belonged too. This was corrected at inspection when the director labeled the bottled in the fridge with the infants name.
Yes
3 746.1309(a) - Documented Annual Training Area - 24 Hours Required
One caregiver did not have the required 24 hours of training.
3 746.2409(a)(10) - Safety Requirements for Cribs - Label for Each Infant
The cribs in the infant room were labeled with number but did not have a crib chart to associate who the crib belonged to. This was corrected at inspection when the director labeled each crib with the infants information.
Yes
4 746.1315(a) - Each Caregiver and the Director Must Have Current Training in pediatric first aid with rescue breathing and choking.
Four caregiver to include the director did not have a first aid certification.
4 746.2419(6) - Requirements for Feeding Infants - Label Bottles/Cups
There were 2 bottles in the infant fridge that were not labeled with the infants name to designate who they belonged too. This was corrected at inspection when the director labeled the bottled in the fridge with the infants name.
Yes
3 745.651(2)(A) - Background Check Validation ? Every 3 months each operation, other than a licensed, registered, or listed home, must validate current list
Employee validation has not been completed since 4.21.2022.
3 746.1309(a) - Documented Annual Training Area - 24 Hours Required
One caregiver did not have the required 24 hours of training.
5 746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months
There was no current fire inspection report available to review during the inspection.
4 746.5537(a)(2) - Electronic or Battery-Operated Carbon Monoxide Detector-Check All Detectors Monthly
The operation did not do any monthly testing for the carbon monoxide this year. This was corrected at inspection when the director tested the carbon monoxide detector.
Yes
5 746.5319 - Smoke Detectors Testing
The operation did not do any monthly testing for the smoke detector this year. This was corrected at inspection when the director tested the smoke detector.
Yes
4 746.5205(1) - Fire Drill Monthly - Exit in 3 Minutes
The fire drill for November 2022 was not completed. This was corrected at inspection when the director conducted a fire drill.
Yes
3 746.2409(a)(10) - Safety Requirements for Cribs - Label for Each Infant
The cribs in the infant room were labeled with number but did not have a crib chart to associate who the crib belonged to. This was corrected at inspection when the director labeled each crib with the infants information.
Yes
3 745.651(2)(A) - Background Check Validation ? Every 3 months each operation, other than a licensed, registered, or listed home, must validate current list
Employee validation has not been completed since 4.21.2022.
3 746.1309(a) - Documented Annual Training Area - 24 Hours Required
One caregiver did not have the required 24 hours of training.
4 746.2419(6) - Requirements for Feeding Infants - Label Bottles/Cups
There were 2 bottles in the infant fridge that were not labeled with the infants name to designate who they belonged too. This was corrected at inspection when the director labeled the bottled in the fridge with the infants name.
Yes
4 746.1315(a) - Each Caregiver and the Director Must Have Current Training in pediatric first aid with rescue breathing and choking.
Four caregiver to include the director did not have a first aid certification.
5 746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months
There was no current fire inspection report available to review during the inspection.
4 746.5537(a)(2) - Electronic or Battery-Operated Carbon Monoxide Detector-Check All Detectors Monthly
The operation did not do any monthly testing for the carbon monoxide this year. This was corrected at inspection when the director tested the carbon monoxide detector.
Yes
5 746.5319 - Smoke Detectors Testing
The operation did not do any monthly testing for the smoke detector this year. This was corrected at inspection when the director tested the smoke detector.
Yes
4 746.5205(1) - Fire Drill Monthly - Exit in 3 Minutes
The fire drill for November 2022 was not completed. This was corrected at inspection when the director conducted a fire drill.
Yes
3 746.2409(a)(10) - Safety Requirements for Cribs - Label for Each Infant
The cribs in the infant room were labeled with number but did not have a crib chart to associate who the crib belonged to. This was corrected at inspection when the director labeled each crib with the infants information.
Yes
5 746.5319 - Smoke Detectors Testing
The operation did not do any monthly testing for the smoke detector this year. This was corrected at inspection when the director tested the smoke detector.
Yes
3 746.2409(a)(10) - Safety Requirements for Cribs - Label for Each Infant
The cribs in the infant room were labeled with number but did not have a crib chart to associate who the crib belonged to. This was corrected at inspection when the director labeled each crib with the infants information.
Yes
4 746.5537(a)(2) - Electronic or Battery-Operated Carbon Monoxide Detector-Check All Detectors Monthly
The operation did not do any monthly testing for the carbon monoxide this year. This was corrected at inspection when the director tested the carbon monoxide detector.
Yes
4 746.1315(a) - Each Caregiver and the Director Must Have Current Training in pediatric first aid with rescue breathing and choking.
Four caregiver to include the director did not have a first aid certification.
5 746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months
There was no current fire inspection report available to review during the inspection.
3 746.1309(a) - Documented Annual Training Area - 24 Hours Required
One caregiver did not have the required 24 hours of training.
3 745.651(2)(A) - Background Check Validation ? Every 3 months each operation, other than a licensed, registered, or listed home, must validate current list
Employee validation has not been completed since 4.21.2022.
4 746.2419(6) - Requirements for Feeding Infants - Label Bottles/Cups
There were 2 bottles in the infant fridge that were not labeled with the infants name to designate who they belonged too. This was corrected at inspection when the director labeled the bottled in the fridge with the infants name.
Yes
4 746.5205(1) - Fire Drill Monthly - Exit in 3 Minutes
The fire drill for November 2022 was not completed. This was corrected at inspection when the director conducted a fire drill.
Yes
4 746.5205(1) - Fire Drill Monthly - Exit in 3 Minutes
The fire drill for November 2022 was not completed. This was corrected at inspection when the director conducted a fire drill.
Yes
3 746.1309(a) - Documented Annual Training Area - 24 Hours Required
One caregiver did not have the required 24 hours of training.
5 746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months
There was no current fire inspection report available to review during the inspection.
4 746.5537(a)(2) - Electronic or Battery-Operated Carbon Monoxide Detector-Check All Detectors Monthly
The operation did not do any monthly testing for the carbon monoxide this year. This was corrected at inspection when the director tested the carbon monoxide detector.
Yes
4 746.1315(a) - Each Caregiver and the Director Must Have Current Training in pediatric first aid with rescue breathing and choking.
Four caregiver to include the director did not have a first aid certification.
3 745.651(2)(A) - Background Check Validation ? Every 3 months each operation, other than a licensed, registered, or listed home, must validate current list
Employee validation has not been completed since 4.21.2022.
5 746.5319 - Smoke Detectors Testing
The operation did not do any monthly testing for the smoke detector this year. This was corrected at inspection when the director tested the smoke detector.
Yes
3 746.2409(a)(10) - Safety Requirements for Cribs - Label for Each Infant
The cribs in the infant room were labeled with number but did not have a crib chart to associate who the crib belonged to. This was corrected at inspection when the director labeled each crib with the infants information.
Yes
4 746.2419(6) - Requirements for Feeding Infants - Label Bottles/Cups
There were 2 bottles in the infant fridge that were not labeled with the infants name to designate who they belonged too. This was corrected at inspection when the director labeled the bottled in the fridge with the infants name.
Yes
4 746.2419(6) - Requirements for Feeding Infants - Label Bottles/Cups
There were 2 bottles in the infant fridge that were not labeled with the infants name to designate who they belonged too. This was corrected at inspection when the director labeled the bottled in the fridge with the infants name.
Yes
3 746.1309(a) - Documented Annual Training Area - 24 Hours Required
One caregiver did not have the required 24 hours of training.
3 746.2409(a)(10) - Safety Requirements for Cribs - Label for Each Infant
The cribs in the infant room were labeled with number but did not have a crib chart to associate who the crib belonged to. This was corrected at inspection when the director labeled each crib with the infants information.
Yes
5 746.5319 - Smoke Detectors Testing
The operation did not do any monthly testing for the smoke detector this year. This was corrected at inspection when the director tested the smoke detector.
Yes
4 746.5205(1) - Fire Drill Monthly - Exit in 3 Minutes
The fire drill for November 2022 was not completed. This was corrected at inspection when the director conducted a fire drill.
Yes
4 746.1315(a) - Each Caregiver and the Director Must Have Current Training in pediatric first aid with rescue breathing and choking.
Four caregiver to include the director did not have a first aid certification.
5 746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months
There was no current fire inspection report available to review during the inspection.
3 745.651(2)(A) - Background Check Validation ? Every 3 months each operation, other than a licensed, registered, or listed home, must validate current list
Employee validation has not been completed since 4.21.2022.
4 746.5537(a)(2) - Electronic or Battery-Operated Carbon Monoxide Detector-Check All Detectors Monthly
The operation did not do any monthly testing for the carbon monoxide this year. This was corrected at inspection when the director tested the carbon monoxide detector.
Yes
4 746.5205(1) - Fire Drill Monthly - Exit in 3 Minutes
The fire drill for November 2022 was not completed. This was corrected at inspection when the director conducted a fire drill.
Yes
3 745.651(2)(A) - Background Check Validation ? Every 3 months each operation, other than a licensed, registered, or listed home, must validate current list
Employee validation has not been completed since 4.21.2022.
3 746.1309(a) - Documented Annual Training Area - 24 Hours Required
One caregiver did not have the required 24 hours of training.
5 746.5319 - Smoke Detectors Testing
The operation did not do any monthly testing for the smoke detector this year. This was corrected at inspection when the director tested the smoke detector.
Yes
4 746.1315(a) - Each Caregiver and the Director Must Have Current Training in pediatric first aid with rescue breathing and choking.
Four caregiver to include the director did not have a first aid certification.
5 746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months
There was no current fire inspection report available to review during the inspection.
4 746.5537(a)(2) - Electronic or Battery-Operated Carbon Monoxide Detector-Check All Detectors Monthly
The operation did not do any monthly testing for the carbon monoxide this year. This was corrected at inspection when the director tested the carbon monoxide detector.
Yes
3 746.2409(a)(10) - Safety Requirements for Cribs - Label for Each Infant
The cribs in the infant room were labeled with number but did not have a crib chart to associate who the crib belonged to. This was corrected at inspection when the director labeled each crib with the infants information.
Yes
4 746.2419(6) - Requirements for Feeding Infants - Label Bottles/Cups
There were 2 bottles in the infant fridge that were not labeled with the infants name to designate who they belonged too. This was corrected at inspection when the director labeled the bottled in the fridge with the infants name.
Yes

Severity 5 = most serious. Source: official state record.

Inspections (16)

16 inspection record(s) on file from TX-HHSC.

Nearby alternatives

FacilityScoreCityDistance
Catholic Charities Of The Archdiocese Of Galveston -Houston 0 Houston
Spring Branch Presbyterian Academy 0 Houston
Wonderland Private School 0 Houston
Trotter YMCA Child Care Center 0 Houston
School of the Woods #1 0 Houston
Terrace Weekday Programs 0 Houston

Licensed facilities near this one, highest compliance score first.

Get violation alerts for this daycare

We'll email you when a new inspection or violation is posted. Free.