DaycareLens
TexasDanbury › Children's Club House Daycare & Learning Center

Children's Club House Daycare & Learning Center

Child care center · 1610 MAIN ST, Danbury, TX 77534-8780 · License 1695763

0Compliance score
Poor

Capacity 106. InfantToddlerPre-KindergartenSchool Accepts subsidy

Violation history (112)

SeverityDateStandard / narrativeCorrected
4 746.3407 - Maintenance of Building, Grounds and Equipment
The air vents in the school age room were visibly dusty. Note: The vents were dusted during my inspection. Pictures were taken of the dirty vents and clean vents.
Yes
5 746.5317 - Installation of Smoke Detectors
At least three of the smoke detectors were beeping indicating low batteries. Note: The batteries were replaced during my inspection.
Yes
3 746.5205(4) - Documentation of Drills
Due to renovations the director cannot find the emergency drill log. Note: The director is continuing to look for the log.
4 746.3407(9) - Floors, ceilings and Walls in Good Repair and Clean
Vents in the toddler room were visibly dusty. A fan in the infant room was dusty. Note: The vents were cleaned and the fan removed from the room during my inspection.
Yes
4 746.1315(a) - Each Caregiver and the Director Must Have Current Training in pediatric first aid with rescue breathing and choking.
The caregivers and director do not have current CPR. Their CPR expired in June of 2025. Note: The director informed me it was scheduled for 6/21/25; however, due to the AC breaking and repairs needed the class was set to be rescheduled.
4 746.3701(5) - Safety - Play Materials and Equipment Safe
The climbing structure was observed to have several spots where the metal was rusting and the protective covering was peeling away from the stairs and platform. The boarder around the climbing structure is broken in several places causing sharp edges. Note: The director and caregiver blocked the entire climbing structure and loose fill area off until they can get it repaired. This brought it into compliance during my inspection.
Yes
3 746.801(5) - Required Records Maintained and Made Available - Employees' Attendance
Sign in and out logs were not readily available for a few of the caregivers and the director during my inspection.
4 746.3407(8) - Garbage Inaccessible to Children; Maintained in Sanitary Manner
Roach activity and live roaches were observed in the kitchen area. Note: Pest control does come out regularly. Pest control was scheduled for Friday with a request for a different formula.
3 746.5205(4) - Documentation of Drills
The emergency drill log could not be found during the inspection.
4 746.4901(b) - Active Play Surfacing In Use Zones - height=depth
A free standing arch climber that does not have loose fill under or around the use zones.
3 746.603(a)(4) - Children's Records - Immunizations
One child's file out of six reviewed does not have current immunization records.
4 746.4907(a)(1) - Installation and Maintenance of Loose-fill Surfacing - Six Inches if Equipment 5 Ft or Less
The loose fill under and around the climbing structure was not 6 inches per required. Note: The director and caregiver blocked off the area of the climbing structure and loose fill so no children can play in the area until repairs can be made. This brought it into compliance.
Yes
4 746.3407(8) - Garbage Inaccessible to Children; Maintained in Sanitary Manner
Follow up 11/14/24: There is still roach activity in the kitchen. Note: Pest control has been twice since the last inspection.
4 746.5103 - Documentation of Fire Inspection
Due to the renoventions the director cannot find the fire inspection report.
4 746.5103 - Documentation of Fire Inspection
Due to the renoventions the director cannot find the fire inspection report.
4 746.4907(a)(1) - Installation and Maintenance of Loose-fill Surfacing - Six Inches if Equipment 5 Ft or Less
The loose fill under and around the climbing structure was not 6 inches per required. Note: The director and caregiver blocked off the area of the climbing structure and loose fill so no children can play in the area until repairs can be made. This brought it into compliance.
Yes
4 746.3701(5) - Safety - Play Materials and Equipment Safe
The climbing structure was observed to have several spots where the metal was rusting and the protective covering was peeling away from the stairs and platform. The boarder around the climbing structure is broken in several places causing sharp edges. Note: The director and caregiver blocked the entire climbing structure and loose fill area off until they can get it repaired. This brought it into compliance during my inspection.
Yes
5 746.5317 - Installation of Smoke Detectors
At least three of the smoke detectors were beeping indicating low batteries. Note: The batteries were replaced during my inspection.
Yes
4 746.3407(9) - Floors, ceilings and Walls in Good Repair and Clean
Vents in the toddler room were visibly dusty. A fan in the infant room was dusty. Note: The vents were cleaned and the fan removed from the room during my inspection.
Yes
3 746.801(5) - Required Records Maintained and Made Available - Employees' Attendance
Sign in and out logs were not readily available for a few of the caregivers and the director during my inspection.
4 746.4901(b) - Active Play Surfacing In Use Zones - height=depth
A free standing arch climber that does not have loose fill under or around the use zones.
4 746.1315(a) - Each Caregiver and the Director Must Have Current Training in pediatric first aid with rescue breathing and choking.
The caregivers and director do not have current CPR. Their CPR expired in June of 2025. Note: The director informed me it was scheduled for 6/21/25; however, due to the AC breaking and repairs needed the class was set to be rescheduled.
3 746.603(a)(4) - Children's Records - Immunizations
One child's file out of six reviewed does not have current immunization records.
3 746.5205(4) - Documentation of Drills
Due to renovations the director cannot find the emergency drill log. Note: The director is continuing to look for the log.
4 746.3407 - Maintenance of Building, Grounds and Equipment
The air vents in the school age room were visibly dusty. Note: The vents were dusted during my inspection. Pictures were taken of the dirty vents and clean vents.
Yes
4 746.3407(8) - Garbage Inaccessible to Children; Maintained in Sanitary Manner
Roach activity and live roaches were observed in the kitchen area. Note: Pest control does come out regularly. Pest control was scheduled for Friday with a request for a different formula.
3 746.5205(4) - Documentation of Drills
The emergency drill log could not be found during the inspection.
4 746.3407(8) - Garbage Inaccessible to Children; Maintained in Sanitary Manner
Follow up 11/14/24: There is still roach activity in the kitchen. Note: Pest control has been twice since the last inspection.
4 746.5103 - Documentation of Fire Inspection
Due to the renoventions the director cannot find the fire inspection report.
4 746.3407(8) - Garbage Inaccessible to Children; Maintained in Sanitary Manner
Follow up 11/14/24: There is still roach activity in the kitchen. Note: Pest control has been twice since the last inspection.
5 746.5317 - Installation of Smoke Detectors
At least three of the smoke detectors were beeping indicating low batteries. Note: The batteries were replaced during my inspection.
Yes
4 746.3407(9) - Floors, ceilings and Walls in Good Repair and Clean
Vents in the toddler room were visibly dusty. A fan in the infant room was dusty. Note: The vents were cleaned and the fan removed from the room during my inspection.
Yes
4 746.4907(a)(1) - Installation and Maintenance of Loose-fill Surfacing - Six Inches if Equipment 5 Ft or Less
The loose fill under and around the climbing structure was not 6 inches per required. Note: The director and caregiver blocked off the area of the climbing structure and loose fill so no children can play in the area until repairs can be made. This brought it into compliance.
Yes
3 746.603(a)(4) - Children's Records - Immunizations
One child's file out of six reviewed does not have current immunization records.
3 746.5205(4) - Documentation of Drills
The emergency drill log could not be found during the inspection.
4 746.5103 - Documentation of Fire Inspection
Due to the renoventions the director cannot find the fire inspection report.
3 746.801(5) - Required Records Maintained and Made Available - Employees' Attendance
Sign in and out logs were not readily available for a few of the caregivers and the director during my inspection.
4 746.4901(b) - Active Play Surfacing In Use Zones - height=depth
A free standing arch climber that does not have loose fill under or around the use zones.
4 746.1315(a) - Each Caregiver and the Director Must Have Current Training in pediatric first aid with rescue breathing and choking.
The caregivers and director do not have current CPR. Their CPR expired in June of 2025. Note: The director informed me it was scheduled for 6/21/25; however, due to the AC breaking and repairs needed the class was set to be rescheduled.
4 746.3701(5) - Safety - Play Materials and Equipment Safe
The climbing structure was observed to have several spots where the metal was rusting and the protective covering was peeling away from the stairs and platform. The boarder around the climbing structure is broken in several places causing sharp edges. Note: The director and caregiver blocked the entire climbing structure and loose fill area off until they can get it repaired. This brought it into compliance during my inspection.
Yes
4 746.3407 - Maintenance of Building, Grounds and Equipment
The air vents in the school age room were visibly dusty. Note: The vents were dusted during my inspection. Pictures were taken of the dirty vents and clean vents.
Yes
4 746.3407(8) - Garbage Inaccessible to Children; Maintained in Sanitary Manner
Roach activity and live roaches were observed in the kitchen area. Note: Pest control does come out regularly. Pest control was scheduled for Friday with a request for a different formula.
3 746.5205(4) - Documentation of Drills
Due to renovations the director cannot find the emergency drill log. Note: The director is continuing to look for the log.
3 746.5205(4) - Documentation of Drills
The emergency drill log could not be found during the inspection.
4 746.4901(b) - Active Play Surfacing In Use Zones - height=depth
A free standing arch climber that does not have loose fill under or around the use zones.
4 746.3407(8) - Garbage Inaccessible to Children; Maintained in Sanitary Manner
Follow up 11/14/24: There is still roach activity in the kitchen. Note: Pest control has been twice since the last inspection.
4 746.1315(a) - Each Caregiver and the Director Must Have Current Training in pediatric first aid with rescue breathing and choking.
The caregivers and director do not have current CPR. Their CPR expired in June of 2025. Note: The director informed me it was scheduled for 6/21/25; however, due to the AC breaking and repairs needed the class was set to be rescheduled.
4 746.3407 - Maintenance of Building, Grounds and Equipment
The air vents in the school age room were visibly dusty. Note: The vents were dusted during my inspection. Pictures were taken of the dirty vents and clean vents.
Yes
3 746.801(5) - Required Records Maintained and Made Available - Employees' Attendance
Sign in and out logs were not readily available for a few of the caregivers and the director during my inspection.
5 746.5317 - Installation of Smoke Detectors
At least three of the smoke detectors were beeping indicating low batteries. Note: The batteries were replaced during my inspection.
Yes
4 746.3407(8) - Garbage Inaccessible to Children; Maintained in Sanitary Manner
Roach activity and live roaches were observed in the kitchen area. Note: Pest control does come out regularly. Pest control was scheduled for Friday with a request for a different formula.
4 746.3407(9) - Floors, ceilings and Walls in Good Repair and Clean
Vents in the toddler room were visibly dusty. A fan in the infant room was dusty. Note: The vents were cleaned and the fan removed from the room during my inspection.
Yes
3 746.603(a)(4) - Children's Records - Immunizations
One child's file out of six reviewed does not have current immunization records.
4 746.5103 - Documentation of Fire Inspection
Due to the renoventions the director cannot find the fire inspection report.
3 746.5205(4) - Documentation of Drills
Due to renovations the director cannot find the emergency drill log. Note: The director is continuing to look for the log.
4 746.3701(5) - Safety - Play Materials and Equipment Safe
The climbing structure was observed to have several spots where the metal was rusting and the protective covering was peeling away from the stairs and platform. The boarder around the climbing structure is broken in several places causing sharp edges. Note: The director and caregiver blocked the entire climbing structure and loose fill area off until they can get it repaired. This brought it into compliance during my inspection.
Yes
4 746.4907(a)(1) - Installation and Maintenance of Loose-fill Surfacing - Six Inches if Equipment 5 Ft or Less
The loose fill under and around the climbing structure was not 6 inches per required. Note: The director and caregiver blocked off the area of the climbing structure and loose fill so no children can play in the area until repairs can be made. This brought it into compliance.
Yes
4 746.3407(8) - Garbage Inaccessible to Children; Maintained in Sanitary Manner
Follow up 11/14/24: There is still roach activity in the kitchen. Note: Pest control has been twice since the last inspection.
4 746.1315(a) - Each Caregiver and the Director Must Have Current Training in pediatric first aid with rescue breathing and choking.
The caregivers and director do not have current CPR. Their CPR expired in June of 2025. Note: The director informed me it was scheduled for 6/21/25; however, due to the AC breaking and repairs needed the class was set to be rescheduled.
4 746.3407(8) - Garbage Inaccessible to Children; Maintained in Sanitary Manner
Roach activity and live roaches were observed in the kitchen area. Note: Pest control does come out regularly. Pest control was scheduled for Friday with a request for a different formula.
4 746.3407 - Maintenance of Building, Grounds and Equipment
The air vents in the school age room were visibly dusty. Note: The vents were dusted during my inspection. Pictures were taken of the dirty vents and clean vents.
Yes
3 746.5205(4) - Documentation of Drills
Due to renovations the director cannot find the emergency drill log. Note: The director is continuing to look for the log.
3 746.5205(4) - Documentation of Drills
The emergency drill log could not be found during the inspection.
5 746.5317 - Installation of Smoke Detectors
At least three of the smoke detectors were beeping indicating low batteries. Note: The batteries were replaced during my inspection.
Yes
4 746.4901(b) - Active Play Surfacing In Use Zones - height=depth
A free standing arch climber that does not have loose fill under or around the use zones.
3 746.801(5) - Required Records Maintained and Made Available - Employees' Attendance
Sign in and out logs were not readily available for a few of the caregivers and the director during my inspection.
4 746.3701(5) - Safety - Play Materials and Equipment Safe
The climbing structure was observed to have several spots where the metal was rusting and the protective covering was peeling away from the stairs and platform. The boarder around the climbing structure is broken in several places causing sharp edges. Note: The director and caregiver blocked the entire climbing structure and loose fill area off until they can get it repaired. This brought it into compliance during my inspection.
Yes
4 746.4907(a)(1) - Installation and Maintenance of Loose-fill Surfacing - Six Inches if Equipment 5 Ft or Less
The loose fill under and around the climbing structure was not 6 inches per required. Note: The director and caregiver blocked off the area of the climbing structure and loose fill so no children can play in the area until repairs can be made. This brought it into compliance.
Yes
4 746.3407(9) - Floors, ceilings and Walls in Good Repair and Clean
Vents in the toddler room were visibly dusty. A fan in the infant room was dusty. Note: The vents were cleaned and the fan removed from the room during my inspection.
Yes
3 746.603(a)(4) - Children's Records - Immunizations
One child's file out of six reviewed does not have current immunization records.
4 746.3407 - Maintenance of Building, Grounds and Equipment
The air vents in the school age room were visibly dusty. Note: The vents were dusted during my inspection. Pictures were taken of the dirty vents and clean vents.
Yes
3 746.5205(4) - Documentation of Drills
Due to renovations the director cannot find the emergency drill log. Note: The director is continuing to look for the log.
4 746.3407(9) - Floors, ceilings and Walls in Good Repair and Clean
Vents in the toddler room were visibly dusty. A fan in the infant room was dusty. Note: The vents were cleaned and the fan removed from the room during my inspection.
Yes
4 746.4901(b) - Active Play Surfacing In Use Zones - height=depth
A free standing arch climber that does not have loose fill under or around the use zones.
4 746.5103 - Documentation of Fire Inspection
Due to the renoventions the director cannot find the fire inspection report.
3 746.801(5) - Required Records Maintained and Made Available - Employees' Attendance
Sign in and out logs were not readily available for a few of the caregivers and the director during my inspection.
4 746.3701(5) - Safety - Play Materials and Equipment Safe
The climbing structure was observed to have several spots where the metal was rusting and the protective covering was peeling away from the stairs and platform. The boarder around the climbing structure is broken in several places causing sharp edges. Note: The director and caregiver blocked the entire climbing structure and loose fill area off until they can get it repaired. This brought it into compliance during my inspection.
Yes
4 746.1315(a) - Each Caregiver and the Director Must Have Current Training in pediatric first aid with rescue breathing and choking.
The caregivers and director do not have current CPR. Their CPR expired in June of 2025. Note: The director informed me it was scheduled for 6/21/25; however, due to the AC breaking and repairs needed the class was set to be rescheduled.
3 746.603(a)(4) - Children's Records - Immunizations
One child's file out of six reviewed does not have current immunization records.
4 746.3407(8) - Garbage Inaccessible to Children; Maintained in Sanitary Manner
Follow up 11/14/24: There is still roach activity in the kitchen. Note: Pest control has been twice since the last inspection.
5 746.5317 - Installation of Smoke Detectors
At least three of the smoke detectors were beeping indicating low batteries. Note: The batteries were replaced during my inspection.
Yes
4 746.4907(a)(1) - Installation and Maintenance of Loose-fill Surfacing - Six Inches if Equipment 5 Ft or Less
The loose fill under and around the climbing structure was not 6 inches per required. Note: The director and caregiver blocked off the area of the climbing structure and loose fill so no children can play in the area until repairs can be made. This brought it into compliance.
Yes
4 746.3407(8) - Garbage Inaccessible to Children; Maintained in Sanitary Manner
Roach activity and live roaches were observed in the kitchen area. Note: Pest control does come out regularly. Pest control was scheduled for Friday with a request for a different formula.
3 746.5205(4) - Documentation of Drills
The emergency drill log could not be found during the inspection.
5 746.5317 - Installation of Smoke Detectors
At least three of the smoke detectors were beeping indicating low batteries. Note: The batteries were replaced during my inspection.
Yes
4 746.3407(8) - Garbage Inaccessible to Children; Maintained in Sanitary Manner
Follow up 11/14/24: There is still roach activity in the kitchen. Note: Pest control has been twice since the last inspection.
4 746.4901(b) - Active Play Surfacing In Use Zones - height=depth
A free standing arch climber that does not have loose fill under or around the use zones.
4 746.3701(5) - Safety - Play Materials and Equipment Safe
The climbing structure was observed to have several spots where the metal was rusting and the protective covering was peeling away from the stairs and platform. The boarder around the climbing structure is broken in several places causing sharp edges. Note: The director and caregiver blocked the entire climbing structure and loose fill area off until they can get it repaired. This brought it into compliance during my inspection.
Yes
4 746.1315(a) - Each Caregiver and the Director Must Have Current Training in pediatric first aid with rescue breathing and choking.
The caregivers and director do not have current CPR. Their CPR expired in June of 2025. Note: The director informed me it was scheduled for 6/21/25; however, due to the AC breaking and repairs needed the class was set to be rescheduled.
3 746.801(5) - Required Records Maintained and Made Available - Employees' Attendance
Sign in and out logs were not readily available for a few of the caregivers and the director during my inspection.
4 746.5103 - Documentation of Fire Inspection
Due to the renoventions the director cannot find the fire inspection report.
4 746.3407(8) - Garbage Inaccessible to Children; Maintained in Sanitary Manner
Roach activity and live roaches were observed in the kitchen area. Note: Pest control does come out regularly. Pest control was scheduled for Friday with a request for a different formula.
4 746.3407 - Maintenance of Building, Grounds and Equipment
The air vents in the school age room were visibly dusty. Note: The vents were dusted during my inspection. Pictures were taken of the dirty vents and clean vents.
Yes
4 746.4907(a)(1) - Installation and Maintenance of Loose-fill Surfacing - Six Inches if Equipment 5 Ft or Less
The loose fill under and around the climbing structure was not 6 inches per required. Note: The director and caregiver blocked off the area of the climbing structure and loose fill so no children can play in the area until repairs can be made. This brought it into compliance.
Yes
3 746.5205(4) - Documentation of Drills
Due to renovations the director cannot find the emergency drill log. Note: The director is continuing to look for the log.
4 746.3407(9) - Floors, ceilings and Walls in Good Repair and Clean
Vents in the toddler room were visibly dusty. A fan in the infant room was dusty. Note: The vents were cleaned and the fan removed from the room during my inspection.
Yes
3 746.5205(4) - Documentation of Drills
The emergency drill log could not be found during the inspection.
3 746.603(a)(4) - Children's Records - Immunizations
One child's file out of six reviewed does not have current immunization records.
4 746.3407(8) - Garbage Inaccessible to Children; Maintained in Sanitary Manner
Roach activity and live roaches were observed in the kitchen area. Note: Pest control does come out regularly. Pest control was scheduled for Friday with a request for a different formula.
4 746.4907(a)(1) - Installation and Maintenance of Loose-fill Surfacing - Six Inches if Equipment 5 Ft or Less
The loose fill under and around the climbing structure was not 6 inches per required. Note: The director and caregiver blocked off the area of the climbing structure and loose fill so no children can play in the area until repairs can be made. This brought it into compliance.
Yes

Severity 5 = most serious. Source: official state record.

Inspections (48)

48 inspection record(s) on file from TX-HHSC.

Nearby alternatives

FacilityScoreCityDistance
First Baptist Child Care Center 0 Highlands
Academy Learning Center 0 Pasadena
Deer Park Methodist Weekday SC 0 Deer Park
La Petite Spencer 0 La Porte
Moody Methodist Day School 0 Galveston
Alvin College Child Development Laboratory School 0 Alvin

Licensed facilities near this one, highest compliance score first.

Get violation alerts for this daycare

We'll email you when a new inspection or violation is posted. Free.