| Severity | Date | Standard / narrative | Corrected |
|---|
| 3 | — |
746.605(10) - Required Admission Information - Physician Information Two children's files do not have medical emergency facility or physician information. |
— |
| 4 | — |
746.3701(1) - Safety - Electrical Outlets Covered The outlet socket was not covered in the PreK class. Note: This was corrected at inspection when the caregiver covered the outlet. |
Yes |
| 4 | — |
746.4751(c) - Maintenance Procedures for Active Play - Hazards Removed or Repaired I observe playground with hazards including small piece of the roof loose and mulch depleted around climbing equipment. |
— |
| 5 | — |
746.605(11) - Required Admission Information - Emergency Medical Authorization Two children's files do not have authorization to obtain emergency medical care. |
— |
| 4 | — |
746.5401 - Requirement of Gas Leak Inspection The operation does not have a recent gas inspection. |
— |
| 2 | — |
746.901(4) - Required Personnel Records - Required Affidavit (Form 2985) One staff file does not have a notarized affidavit. |
— |
| 4 | — |
746.5205(1) - Fire Drill Monthly - Exit in 3 Minutes The operation staff/children are not exiting the building during a fire drill within the required 3 minutes. Most of the documented drill (January - March 2022) exit times have been 5 minutes or more. |
— |
| 4 | — |
746.401(10) - Required Postings-Child's Food Allergies There was no allergy posting of a child that has known food allergies. |
— |
| 4 | — |
746.2419(6) - Requirements for Feeding Infants - Label Bottles/Cups I observe several feeding bottles and training cups in the infant room not labeled with child's name. |
— |
| 4 | — |
746.3407 - Maintenance of Building, Grounds and Equipment The outdoor area plastic covering over the table was ripped in different places. This could be hazardous to the children. |
— |
| 4 | — |
746.5401 - Requirement of Gas Leak Inspection The operation does not have a recent gas inspection. |
— |
| 5 | — |
746.613(a) - Required Immunizations One out of five files did not have immunizations available for review during the inspection. |
— |
| 3 | — |
746.4135(b) - Children's Products- Annual Certification The operation did not have a current consumer product safety commission form during the inspection. |
— |
| 3 | — |
746.1309(a) - Documented Annual Training Area - 24 Hours Required One out of four files was missing 15.25 hours of annual training. |
— |
| 3 | — |
746.801(8) - Required Records Maintained and Made Available - Playground Maintenance Records There was no playground maintenance checklist available for review during the inspection. |
— |
| 4 | — |
746.3407(9) - Floors, ceilings and Walls in Good Repair and Clean The floor in the indoor multipurpose room floor was torn in different places, and it could cause a tripping hazard for the children. Note: This was corrected during inspection when the director covered the torn floor with tape. |
Yes |
| 4 | — |
746.3819 - Food Allergy Emergency Plan Signed by Parents and Health Care Professional A child with known food allergies didi not have a food allergy emergency form for review. |
— |
| 4 | — |
746.2409(a)(2) - Safety Requirements for Cribs - Snug Fitting Sheets The sheets in the crib used by infant did not fit snuggly. Note: corrected during inspection. |
Yes |
| 4 | — |
746.401(10) - Required Postings-Child's Food Allergies There was no allergy posting of a child that has known food allergies. |
— |
| 3 | — |
746.1309(a) - Documented Annual Training Area - 24 Hours Required One out of four files was missing 15.25 hours of annual training. |
— |
| 3 | — |
746.4135(b) - Children's Products- Annual Certification The operation did not have a current consumer product safety commission form during the inspection. |
— |
| 4 | — |
746.4751(c) - Maintenance Procedures for Active Play - Hazards Removed or Repaired I observe playground with hazards including small piece of the roof loose and mulch depleted around climbing equipment. |
— |
| 4 | — |
746.5401 - Requirement of Gas Leak Inspection The operation does not have a recent gas inspection. |
— |
| 2 | — |
746.901(4) - Required Personnel Records - Required Affidavit (Form 2985) One staff file does not have a notarized affidavit. |
— |
| 4 | — |
746.3407(9) - Floors, ceilings and Walls in Good Repair and Clean The floor in the indoor multipurpose room floor was torn in different places, and it could cause a tripping hazard for the children. Note: This was corrected during inspection when the director covered the torn floor with tape. |
Yes |
| 4 | — |
746.2409(a)(2) - Safety Requirements for Cribs - Snug Fitting Sheets The sheets in the crib used by infant did not fit snuggly. Note: corrected during inspection. |
Yes |
| 4 | — |
746.3701(1) - Safety - Electrical Outlets Covered The outlet socket was not covered in the PreK class. Note: This was corrected at inspection when the caregiver covered the outlet. |
Yes |
| 3 | — |
746.801(8) - Required Records Maintained and Made Available - Playground Maintenance Records There was no playground maintenance checklist available for review during the inspection. |
— |
| 4 | — |
746.2419(6) - Requirements for Feeding Infants - Label Bottles/Cups I observe several feeding bottles and training cups in the infant room not labeled with child's name. |
— |
| 4 | — |
746.5205(1) - Fire Drill Monthly - Exit in 3 Minutes The operation staff/children are not exiting the building during a fire drill within the required 3 minutes. Most of the documented drill (January - March 2022) exit times have been 5 minutes or more. |
— |
| 5 | — |
746.613(a) - Required Immunizations One out of five files did not have immunizations available for review during the inspection. |
— |
| 4 | — |
746.3407 - Maintenance of Building, Grounds and Equipment The outdoor area plastic covering over the table was ripped in different places. This could be hazardous to the children. |
— |
| 4 | — |
746.3819 - Food Allergy Emergency Plan Signed by Parents and Health Care Professional A child with known food allergies didi not have a food allergy emergency form for review. |
— |
| 5 | — |
746.605(11) - Required Admission Information - Emergency Medical Authorization Two children's files do not have authorization to obtain emergency medical care. |
— |
| 3 | — |
746.605(10) - Required Admission Information - Physician Information Two children's files do not have medical emergency facility or physician information. |
— |
| 4 | — |
746.5401 - Requirement of Gas Leak Inspection The operation does not have a recent gas inspection. |
— |
| 2 | — |
746.901(4) - Required Personnel Records - Required Affidavit (Form 2985) One staff file does not have a notarized affidavit. |
— |
| 4 | — |
746.2409(a)(2) - Safety Requirements for Cribs - Snug Fitting Sheets The sheets in the crib used by infant did not fit snuggly. Note: corrected during inspection. |
Yes |
| 5 | — |
746.605(11) - Required Admission Information - Emergency Medical Authorization Two children's files do not have authorization to obtain emergency medical care. |
— |
| 4 | — |
746.5401 - Requirement of Gas Leak Inspection The operation does not have a recent gas inspection. |
— |
| 4 | — |
746.3701(1) - Safety - Electrical Outlets Covered The outlet socket was not covered in the PreK class. Note: This was corrected at inspection when the caregiver covered the outlet. |
Yes |
| 4 | — |
746.5205(1) - Fire Drill Monthly - Exit in 3 Minutes The operation staff/children are not exiting the building during a fire drill within the required 3 minutes. Most of the documented drill (January - March 2022) exit times have been 5 minutes or more. |
— |
| 4 | — |
746.4751(c) - Maintenance Procedures for Active Play - Hazards Removed or Repaired I observe playground with hazards including small piece of the roof loose and mulch depleted around climbing equipment. |
— |
| 3 | — |
746.1309(a) - Documented Annual Training Area - 24 Hours Required One out of four files was missing 15.25 hours of annual training. |
— |
| 4 | — |
746.401(10) - Required Postings-Child's Food Allergies There was no allergy posting of a child that has known food allergies. |
— |
| 4 | — |
746.3819 - Food Allergy Emergency Plan Signed by Parents and Health Care Professional A child with known food allergies didi not have a food allergy emergency form for review. |
— |
| 4 | — |
746.5401 - Requirement of Gas Leak Inspection The operation does not have a recent gas inspection. |
— |
| 3 | — |
746.605(10) - Required Admission Information - Physician Information Two children's files do not have medical emergency facility or physician information. |
— |
| 3 | — |
746.801(8) - Required Records Maintained and Made Available - Playground Maintenance Records There was no playground maintenance checklist available for review during the inspection. |
— |
| 4 | — |
746.2419(6) - Requirements for Feeding Infants - Label Bottles/Cups I observe several feeding bottles and training cups in the infant room not labeled with child's name. |
— |
| 5 | — |
746.613(a) - Required Immunizations One out of five files did not have immunizations available for review during the inspection. |
— |
| 4 | — |
746.3407(9) - Floors, ceilings and Walls in Good Repair and Clean The floor in the indoor multipurpose room floor was torn in different places, and it could cause a tripping hazard for the children. Note: This was corrected during inspection when the director covered the torn floor with tape. |
Yes |
| 4 | — |
746.3407 - Maintenance of Building, Grounds and Equipment The outdoor area plastic covering over the table was ripped in different places. This could be hazardous to the children. |
— |
| 3 | — |
746.4135(b) - Children's Products- Annual Certification The operation did not have a current consumer product safety commission form during the inspection. |
— |
| 4 | — |
746.5401 - Requirement of Gas Leak Inspection The operation does not have a recent gas inspection. |
— |
| 4 | — |
746.3701(1) - Safety - Electrical Outlets Covered The outlet socket was not covered in the PreK class. Note: This was corrected at inspection when the caregiver covered the outlet. |
Yes |
| 3 | — |
746.1309(a) - Documented Annual Training Area - 24 Hours Required One out of four files was missing 15.25 hours of annual training. |
— |
| 4 | — |
746.4751(c) - Maintenance Procedures for Active Play - Hazards Removed or Repaired I observe playground with hazards including small piece of the roof loose and mulch depleted around climbing equipment. |
— |
| 4 | — |
746.401(10) - Required Postings-Child's Food Allergies There was no allergy posting of a child that has known food allergies. |
— |
| 4 | — |
746.3819 - Food Allergy Emergency Plan Signed by Parents and Health Care Professional A child with known food allergies didi not have a food allergy emergency form for review. |
— |
| 3 | — |
746.801(8) - Required Records Maintained and Made Available - Playground Maintenance Records There was no playground maintenance checklist available for review during the inspection. |
— |
| 3 | — |
746.605(10) - Required Admission Information - Physician Information Two children's files do not have medical emergency facility or physician information. |
— |
| 4 | — |
746.5401 - Requirement of Gas Leak Inspection The operation does not have a recent gas inspection. |
— |
| 4 | — |
746.2419(6) - Requirements for Feeding Infants - Label Bottles/Cups I observe several feeding bottles and training cups in the infant room not labeled with child's name. |
— |
| 4 | — |
746.3407 - Maintenance of Building, Grounds and Equipment The outdoor area plastic covering over the table was ripped in different places. This could be hazardous to the children. |
— |
| 4 | — |
746.3407(9) - Floors, ceilings and Walls in Good Repair and Clean The floor in the indoor multipurpose room floor was torn in different places, and it could cause a tripping hazard for the children. Note: This was corrected during inspection when the director covered the torn floor with tape. |
Yes |
| 4 | — |
746.5205(1) - Fire Drill Monthly - Exit in 3 Minutes The operation staff/children are not exiting the building during a fire drill within the required 3 minutes. Most of the documented drill (January - March 2022) exit times have been 5 minutes or more. |
— |
| 4 | — |
746.2409(a)(2) - Safety Requirements for Cribs - Snug Fitting Sheets The sheets in the crib used by infant did not fit snuggly. Note: corrected during inspection. |
Yes |
| 5 | — |
746.613(a) - Required Immunizations One out of five files did not have immunizations available for review during the inspection. |
— |
| 5 | — |
746.605(11) - Required Admission Information - Emergency Medical Authorization Two children's files do not have authorization to obtain emergency medical care. |
— |
| 2 | — |
746.901(4) - Required Personnel Records - Required Affidavit (Form 2985) One staff file does not have a notarized affidavit. |
— |
| 3 | — |
746.4135(b) - Children's Products- Annual Certification The operation did not have a current consumer product safety commission form during the inspection. |
— |
| 4 | — |
746.2409(a)(2) - Safety Requirements for Cribs - Snug Fitting Sheets The sheets in the crib used by infant did not fit snuggly. Note: corrected during inspection. |
Yes |
| 4 | — |
746.5401 - Requirement of Gas Leak Inspection The operation does not have a recent gas inspection. |
— |
| 4 | — |
746.3701(1) - Safety - Electrical Outlets Covered The outlet socket was not covered in the PreK class. Note: This was corrected at inspection when the caregiver covered the outlet. |
Yes |
| 4 | — |
746.5205(1) - Fire Drill Monthly - Exit in 3 Minutes The operation staff/children are not exiting the building during a fire drill within the required 3 minutes. Most of the documented drill (January - March 2022) exit times have been 5 minutes or more. |
— |
| 3 | — |
746.1309(a) - Documented Annual Training Area - 24 Hours Required One out of four files was missing 15.25 hours of annual training. |
— |
| 4 | — |
746.3819 - Food Allergy Emergency Plan Signed by Parents and Health Care Professional A child with known food allergies didi not have a food allergy emergency form for review. |
— |
| 3 | — |
746.605(10) - Required Admission Information - Physician Information Two children's files do not have medical emergency facility or physician information. |
— |
| 3 | — |
746.4135(b) - Children's Products- Annual Certification The operation did not have a current consumer product safety commission form during the inspection. |
— |
| 2 | — |
746.901(4) - Required Personnel Records - Required Affidavit (Form 2985) One staff file does not have a notarized affidavit. |
— |
| 4 | — |
746.4751(c) - Maintenance Procedures for Active Play - Hazards Removed or Repaired I observe playground with hazards including small piece of the roof loose and mulch depleted around climbing equipment. |
— |
| 3 | — |
746.801(8) - Required Records Maintained and Made Available - Playground Maintenance Records There was no playground maintenance checklist available for review during the inspection. |
— |
| 4 | — |
746.401(10) - Required Postings-Child's Food Allergies There was no allergy posting of a child that has known food allergies. |
— |
| 4 | — |
746.3407(9) - Floors, ceilings and Walls in Good Repair and Clean The floor in the indoor multipurpose room floor was torn in different places, and it could cause a tripping hazard for the children. Note: This was corrected during inspection when the director covered the torn floor with tape. |
Yes |
| 4 | — |
746.5401 - Requirement of Gas Leak Inspection The operation does not have a recent gas inspection. |
— |
| 4 | — |
746.2419(6) - Requirements for Feeding Infants - Label Bottles/Cups I observe several feeding bottles and training cups in the infant room not labeled with child's name. |
— |
| 5 | — |
746.605(11) - Required Admission Information - Emergency Medical Authorization Two children's files do not have authorization to obtain emergency medical care. |
— |
| 4 | — |
746.3407 - Maintenance of Building, Grounds and Equipment The outdoor area plastic covering over the table was ripped in different places. This could be hazardous to the children. |
— |
| 5 | — |
746.613(a) - Required Immunizations One out of five files did not have immunizations available for review during the inspection. |
— |
| 5 | — |
746.613(a) - Required Immunizations One out of five files did not have immunizations available for review during the inspection. |
— |
| 3 | — |
746.605(10) - Required Admission Information - Physician Information Two children's files do not have medical emergency facility or physician information. |
— |
| 3 | — |
746.1309(a) - Documented Annual Training Area - 24 Hours Required One out of four files was missing 15.25 hours of annual training. |
— |
| 4 | — |
746.3407(9) - Floors, ceilings and Walls in Good Repair and Clean The floor in the indoor multipurpose room floor was torn in different places, and it could cause a tripping hazard for the children. Note: This was corrected during inspection when the director covered the torn floor with tape. |
Yes |
| 5 | — |
746.605(11) - Required Admission Information - Emergency Medical Authorization Two children's files do not have authorization to obtain emergency medical care. |
— |
| 4 | — |
746.4751(c) - Maintenance Procedures for Active Play - Hazards Removed or Repaired I observe playground with hazards including small piece of the roof loose and mulch depleted around climbing equipment. |
— |
| 4 | — |
746.5205(1) - Fire Drill Monthly - Exit in 3 Minutes The operation staff/children are not exiting the building during a fire drill within the required 3 minutes. Most of the documented drill (January - March 2022) exit times have been 5 minutes or more. |
— |
| 3 | — |
746.801(8) - Required Records Maintained and Made Available - Playground Maintenance Records There was no playground maintenance checklist available for review during the inspection. |
— |
| 2 | — |
746.901(4) - Required Personnel Records - Required Affidavit (Form 2985) One staff file does not have a notarized affidavit. |
— |
| 4 | — |
746.5401 - Requirement of Gas Leak Inspection The operation does not have a recent gas inspection. |
— |
56 inspection record(s) on file from TX-HHSC.