Violation history (96)

SeverityDateStandard / narrativeCorrected
5 747.5111 - Smoke-Detection System
There was not a smoke detector available in a room used by children.
2 747.905(2) - Personnel Records for Household Members - Orientation
Household members did not complete an orientation to the child care home.
4 747.5105 - Mounting of Fire Extinguishers
Fire extinguisher was not mounted properly on the wall.
4 747.5107(a) - Inspect Fire Extinguishers Monthly
Fire extinguishers inspections were not recorded when done.
4 747.5005(1) - Fire Drill Monthly - Exit in 3 Minutes
Fire drills have not been conducted since the operation opened.
4 747.5005(3) - Lock-down drill 4 times in a calendar year
Lock-down drills has not been conducted in a year.
3 747.3113(1) - Maintain Menus
A menu for the past three months has not been maintained.
3 747.611(b) - Health Statement on File
Two of the three records reviewed did not have a health statement on file.
5 747.5115 - Smoke Detectors Testing
There is no record that the smoke detectors are being tested monthly.
3 747.401(a)(1) - Posting Requirements-License
There was not a parent notification board with all the required postings available to review during the inspection.
4 747.5005(2) - Sheltering drill for Severe Weather- 4 times in a calendar year
Shelter drills has not been conducted within a year.
4 747.5007 - Emergency Evacuation and Relocation Diagram- Must Be On File
There was not an emergency evacuation and diagram available for licensing to review.
4 747.5005(1) - Fire Drill Monthly - Exit in 3 Minutes
Fire drills have not been conducted since the operation opened.
4 747.5105 - Mounting of Fire Extinguishers
Fire extinguisher was not mounted properly on the wall.
4 747.5107(a) - Inspect Fire Extinguishers Monthly
Fire extinguishers inspections were not recorded when done.
5 747.5111 - Smoke-Detection System
There was not a smoke detector available in a room used by children.
4 747.5005(2) - Sheltering drill for Severe Weather- 4 times in a calendar year
Shelter drills has not been conducted within a year.
2 747.905(2) - Personnel Records for Household Members - Orientation
Household members did not complete an orientation to the child care home.
3 747.611(b) - Health Statement on File
Two of the three records reviewed did not have a health statement on file.
5 747.5115 - Smoke Detectors Testing
There is no record that the smoke detectors are being tested monthly.
4 747.5007 - Emergency Evacuation and Relocation Diagram- Must Be On File
There was not an emergency evacuation and diagram available for licensing to review.
3 747.401(a)(1) - Posting Requirements-License
There was not a parent notification board with all the required postings available to review during the inspection.
4 747.5005(3) - Lock-down drill 4 times in a calendar year
Lock-down drills has not been conducted in a year.
3 747.3113(1) - Maintain Menus
A menu for the past three months has not been maintained.
4 747.5105 - Mounting of Fire Extinguishers
Fire extinguisher was not mounted properly on the wall.
3 747.3113(1) - Maintain Menus
A menu for the past three months has not been maintained.
3 747.401(a)(1) - Posting Requirements-License
There was not a parent notification board with all the required postings available to review during the inspection.
3 747.3113(1) - Maintain Menus
A menu for the past three months has not been maintained.
5 747.5115 - Smoke Detectors Testing
There is no record that the smoke detectors are being tested monthly.
4 747.5105 - Mounting of Fire Extinguishers
Fire extinguisher was not mounted properly on the wall.
2 747.905(2) - Personnel Records for Household Members - Orientation
Household members did not complete an orientation to the child care home.
4 747.5005(3) - Lock-down drill 4 times in a calendar year
Lock-down drills has not been conducted in a year.
5 747.5111 - Smoke-Detection System
There was not a smoke detector available in a room used by children.
4 747.5005(2) - Sheltering drill for Severe Weather- 4 times in a calendar year
Shelter drills has not been conducted within a year.
4 747.5007 - Emergency Evacuation and Relocation Diagram- Must Be On File
There was not an emergency evacuation and diagram available for licensing to review.
4 747.5005(1) - Fire Drill Monthly - Exit in 3 Minutes
Fire drills have not been conducted since the operation opened.
4 747.5107(a) - Inspect Fire Extinguishers Monthly
Fire extinguishers inspections were not recorded when done.
3 747.611(b) - Health Statement on File
Two of the three records reviewed did not have a health statement on file.
4 747.5005(1) - Fire Drill Monthly - Exit in 3 Minutes
Fire drills have not been conducted since the operation opened.
5 747.5111 - Smoke-Detection System
There was not a smoke detector available in a room used by children.
2 747.905(2) - Personnel Records for Household Members - Orientation
Household members did not complete an orientation to the child care home.
3 747.611(b) - Health Statement on File
Two of the three records reviewed did not have a health statement on file.
4 747.5107(a) - Inspect Fire Extinguishers Monthly
Fire extinguishers inspections were not recorded when done.
5 747.5115 - Smoke Detectors Testing
There is no record that the smoke detectors are being tested monthly.
4 747.5005(3) - Lock-down drill 4 times in a calendar year
Lock-down drills has not been conducted in a year.
3 747.401(a)(1) - Posting Requirements-License
There was not a parent notification board with all the required postings available to review during the inspection.
3 747.3113(1) - Maintain Menus
A menu for the past three months has not been maintained.
4 747.5007 - Emergency Evacuation and Relocation Diagram- Must Be On File
There was not an emergency evacuation and diagram available for licensing to review.
4 747.5105 - Mounting of Fire Extinguishers
Fire extinguisher was not mounted properly on the wall.
4 747.5005(2) - Sheltering drill for Severe Weather- 4 times in a calendar year
Shelter drills has not been conducted within a year.
5 747.5115 - Smoke Detectors Testing
There is no record that the smoke detectors are being tested monthly.
4 747.5005(3) - Lock-down drill 4 times in a calendar year
Lock-down drills has not been conducted in a year.
3 747.401(a)(1) - Posting Requirements-License
There was not a parent notification board with all the required postings available to review during the inspection.
2 747.905(2) - Personnel Records for Household Members - Orientation
Household members did not complete an orientation to the child care home.
3 747.611(b) - Health Statement on File
Two of the three records reviewed did not have a health statement on file.
4 747.5007 - Emergency Evacuation and Relocation Diagram- Must Be On File
There was not an emergency evacuation and diagram available for licensing to review.
4 747.5107(a) - Inspect Fire Extinguishers Monthly
Fire extinguishers inspections were not recorded when done.
4 747.5005(2) - Sheltering drill for Severe Weather- 4 times in a calendar year
Shelter drills has not been conducted within a year.
4 747.5105 - Mounting of Fire Extinguishers
Fire extinguisher was not mounted properly on the wall.
5 747.5111 - Smoke-Detection System
There was not a smoke detector available in a room used by children.
4 747.5005(1) - Fire Drill Monthly - Exit in 3 Minutes
Fire drills have not been conducted since the operation opened.
3 747.3113(1) - Maintain Menus
A menu for the past three months has not been maintained.
4 747.5105 - Mounting of Fire Extinguishers
Fire extinguisher was not mounted properly on the wall.
3 747.401(a)(1) - Posting Requirements-License
There was not a parent notification board with all the required postings available to review during the inspection.
4 747.5005(1) - Fire Drill Monthly - Exit in 3 Minutes
Fire drills have not been conducted since the operation opened.
3 747.3113(1) - Maintain Menus
A menu for the past three months has not been maintained.
3 747.611(b) - Health Statement on File
Two of the three records reviewed did not have a health statement on file.
4 747.5107(a) - Inspect Fire Extinguishers Monthly
Fire extinguishers inspections were not recorded when done.
4 747.5007 - Emergency Evacuation and Relocation Diagram- Must Be On File
There was not an emergency evacuation and diagram available for licensing to review.
2 747.905(2) - Personnel Records for Household Members - Orientation
Household members did not complete an orientation to the child care home.
5 747.5111 - Smoke-Detection System
There was not a smoke detector available in a room used by children.
5 747.5115 - Smoke Detectors Testing
There is no record that the smoke detectors are being tested monthly.
4 747.5005(3) - Lock-down drill 4 times in a calendar year
Lock-down drills has not been conducted in a year.
4 747.5005(2) - Sheltering drill for Severe Weather- 4 times in a calendar year
Shelter drills has not been conducted within a year.
4 747.5107(a) - Inspect Fire Extinguishers Monthly
Fire extinguishers inspections were not recorded when done.
5 747.5115 - Smoke Detectors Testing
There is no record that the smoke detectors are being tested monthly.
3 747.401(a)(1) - Posting Requirements-License
There was not a parent notification board with all the required postings available to review during the inspection.
5 747.5111 - Smoke-Detection System
There was not a smoke detector available in a room used by children.
3 747.611(b) - Health Statement on File
Two of the three records reviewed did not have a health statement on file.
4 747.5005(2) - Sheltering drill for Severe Weather- 4 times in a calendar year
Shelter drills has not been conducted within a year.
4 747.5005(1) - Fire Drill Monthly - Exit in 3 Minutes
Fire drills have not been conducted since the operation opened.
4 747.5007 - Emergency Evacuation and Relocation Diagram- Must Be On File
There was not an emergency evacuation and diagram available for licensing to review.
2 747.905(2) - Personnel Records for Household Members - Orientation
Household members did not complete an orientation to the child care home.
4 747.5005(3) - Lock-down drill 4 times in a calendar year
Lock-down drills has not been conducted in a year.
4 747.5107(a) - Inspect Fire Extinguishers Monthly
Fire extinguishers inspections were not recorded when done.
5 747.5115 - Smoke Detectors Testing
There is no record that the smoke detectors are being tested monthly.
3 747.611(b) - Health Statement on File
Two of the three records reviewed did not have a health statement on file.
3 747.3113(1) - Maintain Menus
A menu for the past three months has not been maintained.
3 747.401(a)(1) - Posting Requirements-License
There was not a parent notification board with all the required postings available to review during the inspection.
5 747.5111 - Smoke-Detection System
There was not a smoke detector available in a room used by children.
4 747.5007 - Emergency Evacuation and Relocation Diagram- Must Be On File
There was not an emergency evacuation and diagram available for licensing to review.
4 747.5105 - Mounting of Fire Extinguishers
Fire extinguisher was not mounted properly on the wall.
2 747.905(2) - Personnel Records for Household Members - Orientation
Household members did not complete an orientation to the child care home.
4 747.5005(2) - Sheltering drill for Severe Weather- 4 times in a calendar year
Shelter drills has not been conducted within a year.
4 747.5005(3) - Lock-down drill 4 times in a calendar year
Lock-down drills has not been conducted in a year.
4 747.5005(1) - Fire Drill Monthly - Exit in 3 Minutes
Fire drills have not been conducted since the operation opened.

Severity 5 = most serious. Source: official state record.

Inspections (16)

16 inspection record(s) on file from TX-HHSC.

Nearby alternatives

FacilityScoreCityDistance
Catholic Charities Of The Archdiocese Of Galveston -Houston 0 Houston
Spring Branch Presbyterian Academy 0 Houston
Wonderland Private School 0 Houston
Trotter YMCA Child Care Center 0 Houston
School of the Woods #1 0 Houston
Terrace Weekday Programs 0 Houston

Licensed facilities near this one, highest compliance score first.

Get violation alerts for this daycare

We'll email you when a new inspection or violation is posted. Free.