Family child care home ·
8250 PARK PLACE BLVD APT 909, Houston, TX 77017-3141 ·
License 831992
Capacity 12. InfantToddlerPre-KindergartenSchool
| Severity | Date | Standard / narrative | Corrected |
|---|
| 3 | — |
747.801(7) - Records Maintained and Made Available - Safety Drills Documentation I did not observe documentation to show fire drills completed and smoke/ carbone monoxide detector tested for November and December 2025. |
— |
| 3 | — |
747.613(b) - Required Immunizations Records, Exceptions, and Exemptions Current One child was missing an updated immunization record. |
— |
| 4 | — |
747.5007 - Emergency Evacuation and Relocation Diagram- Must Be On File I did not observe emergency evacuation and relocation diagram available for review. |
— |
| 5 | — |
747.5115 - Smoke Detectors Testing Testing of the smoke detectors have not been conducted since March of 2023. This was corrected when the smoke detector was tested during the inspection and documented. |
Yes |
| 4 | — |
747.5005(1) - Fire Drill Monthly - Exit in 3 Minutes Fire drills were not being conducted and documented for the months of April 2023 to December 2023. This was corrected when a fire drill was conducted during the inspection and documented. |
Yes |
| 4 | — |
747.5337(a)(2) - Electric or Battery Operated CO System-Test Monthly The carbon monoxide detector had not been tested monthly and documented since March 2023. This was corrected when the carbon monoxide detector was tested and documented. |
Yes |
| 4 | — |
747.5107(a) - Inspect Fire Extinguishers Monthly There is no documentation of a monthly fire extinguisher inspection being conducted since March 2023. This was corrected when the fire extinguisher was inspected by the caregiver and documented. |
Yes |
| 3 | — |
747.613(b) - Required Immunizations Records, Exceptions, and Exemptions Current One child was missing an updated immunization record. |
— |
| 4 | — |
747.5005(1) - Fire Drill Monthly - Exit in 3 Minutes Fire drills were not being conducted and documented for the months of April 2023 to December 2023. This was corrected when a fire drill was conducted during the inspection and documented. |
Yes |
| 4 | — |
747.5337(a)(2) - Electric or Battery Operated CO System-Test Monthly The carbon monoxide detector had not been tested monthly and documented since March 2023. This was corrected when the carbon monoxide detector was tested and documented. |
Yes |
| 3 | — |
747.801(7) - Records Maintained and Made Available - Safety Drills Documentation I did not observe documentation to show fire drills completed and smoke/ carbone monoxide detector tested for November and December 2025. |
— |
| 4 | — |
747.5007 - Emergency Evacuation and Relocation Diagram- Must Be On File I did not observe emergency evacuation and relocation diagram available for review. |
— |
| 5 | — |
747.5115 - Smoke Detectors Testing Testing of the smoke detectors have not been conducted since March of 2023. This was corrected when the smoke detector was tested during the inspection and documented. |
Yes |
| 4 | — |
747.5107(a) - Inspect Fire Extinguishers Monthly There is no documentation of a monthly fire extinguisher inspection being conducted since March 2023. This was corrected when the fire extinguisher was inspected by the caregiver and documented. |
Yes |
| 5 | — |
747.5115 - Smoke Detectors Testing Testing of the smoke detectors have not been conducted since March of 2023. This was corrected when the smoke detector was tested during the inspection and documented. |
Yes |
| 4 | — |
747.5337(a)(2) - Electric or Battery Operated CO System-Test Monthly The carbon monoxide detector had not been tested monthly and documented since March 2023. This was corrected when the carbon monoxide detector was tested and documented. |
Yes |
| 4 | — |
747.5007 - Emergency Evacuation and Relocation Diagram- Must Be On File I did not observe emergency evacuation and relocation diagram available for review. |
— |
| 4 | — |
747.5005(1) - Fire Drill Monthly - Exit in 3 Minutes Fire drills were not being conducted and documented for the months of April 2023 to December 2023. This was corrected when a fire drill was conducted during the inspection and documented. |
Yes |
| 3 | — |
747.613(b) - Required Immunizations Records, Exceptions, and Exemptions Current One child was missing an updated immunization record. |
— |
| 4 | — |
747.5107(a) - Inspect Fire Extinguishers Monthly There is no documentation of a monthly fire extinguisher inspection being conducted since March 2023. This was corrected when the fire extinguisher was inspected by the caregiver and documented. |
Yes |
| 3 | — |
747.801(7) - Records Maintained and Made Available - Safety Drills Documentation I did not observe documentation to show fire drills completed and smoke/ carbone monoxide detector tested for November and December 2025. |
— |
| 3 | — |
747.613(b) - Required Immunizations Records, Exceptions, and Exemptions Current One child was missing an updated immunization record. |
— |
| 5 | — |
747.5115 - Smoke Detectors Testing Testing of the smoke detectors have not been conducted since March of 2023. This was corrected when the smoke detector was tested during the inspection and documented. |
Yes |
| 3 | — |
747.801(7) - Records Maintained and Made Available - Safety Drills Documentation I did not observe documentation to show fire drills completed and smoke/ carbone monoxide detector tested for November and December 2025. |
— |
| 4 | — |
747.5337(a)(2) - Electric or Battery Operated CO System-Test Monthly The carbon monoxide detector had not been tested monthly and documented since March 2023. This was corrected when the carbon monoxide detector was tested and documented. |
Yes |
| 4 | — |
747.5107(a) - Inspect Fire Extinguishers Monthly There is no documentation of a monthly fire extinguisher inspection being conducted since March 2023. This was corrected when the fire extinguisher was inspected by the caregiver and documented. |
Yes |
| 4 | — |
747.5005(1) - Fire Drill Monthly - Exit in 3 Minutes Fire drills were not being conducted and documented for the months of April 2023 to December 2023. This was corrected when a fire drill was conducted during the inspection and documented. |
Yes |
| 4 | — |
747.5007 - Emergency Evacuation and Relocation Diagram- Must Be On File I did not observe emergency evacuation and relocation diagram available for review. |
— |
| 3 | — |
747.801(7) - Records Maintained and Made Available - Safety Drills Documentation I did not observe documentation to show fire drills completed and smoke/ carbone monoxide detector tested for November and December 2025. |
— |
| 4 | — |
747.5107(a) - Inspect Fire Extinguishers Monthly There is no documentation of a monthly fire extinguisher inspection being conducted since March 2023. This was corrected when the fire extinguisher was inspected by the caregiver and documented. |
Yes |
| 4 | — |
747.5005(1) - Fire Drill Monthly - Exit in 3 Minutes Fire drills were not being conducted and documented for the months of April 2023 to December 2023. This was corrected when a fire drill was conducted during the inspection and documented. |
Yes |
| 4 | — |
747.5007 - Emergency Evacuation and Relocation Diagram- Must Be On File I did not observe emergency evacuation and relocation diagram available for review. |
— |
| 3 | — |
747.613(b) - Required Immunizations Records, Exceptions, and Exemptions Current One child was missing an updated immunization record. |
— |
| 4 | — |
747.5337(a)(2) - Electric or Battery Operated CO System-Test Monthly The carbon monoxide detector had not been tested monthly and documented since March 2023. This was corrected when the carbon monoxide detector was tested and documented. |
Yes |
| 5 | — |
747.5115 - Smoke Detectors Testing Testing of the smoke detectors have not been conducted since March of 2023. This was corrected when the smoke detector was tested during the inspection and documented. |
Yes |
| 5 | — |
747.5115 - Smoke Detectors Testing Testing of the smoke detectors have not been conducted since March of 2023. This was corrected when the smoke detector was tested during the inspection and documented. |
Yes |
| 4 | — |
747.5007 - Emergency Evacuation and Relocation Diagram- Must Be On File I did not observe emergency evacuation and relocation diagram available for review. |
— |
| 3 | — |
747.613(b) - Required Immunizations Records, Exceptions, and Exemptions Current One child was missing an updated immunization record. |
— |
| 4 | — |
747.5337(a)(2) - Electric or Battery Operated CO System-Test Monthly The carbon monoxide detector had not been tested monthly and documented since March 2023. This was corrected when the carbon monoxide detector was tested and documented. |
Yes |
| 4 | — |
747.5005(1) - Fire Drill Monthly - Exit in 3 Minutes Fire drills were not being conducted and documented for the months of April 2023 to December 2023. This was corrected when a fire drill was conducted during the inspection and documented. |
Yes |
| 4 | — |
747.5107(a) - Inspect Fire Extinguishers Monthly There is no documentation of a monthly fire extinguisher inspection being conducted since March 2023. This was corrected when the fire extinguisher was inspected by the caregiver and documented. |
Yes |
| 3 | — |
747.801(7) - Records Maintained and Made Available - Safety Drills Documentation I did not observe documentation to show fire drills completed and smoke/ carbone monoxide detector tested for November and December 2025. |
— |
| 4 | — |
747.5107(a) - Inspect Fire Extinguishers Monthly There is no documentation of a monthly fire extinguisher inspection being conducted since March 2023. This was corrected when the fire extinguisher was inspected by the caregiver and documented. |
Yes |
| 4 | — |
747.5337(a)(2) - Electric or Battery Operated CO System-Test Monthly The carbon monoxide detector had not been tested monthly and documented since March 2023. This was corrected when the carbon monoxide detector was tested and documented. |
Yes |
| 5 | — |
747.5115 - Smoke Detectors Testing Testing of the smoke detectors have not been conducted since March of 2023. This was corrected when the smoke detector was tested during the inspection and documented. |
Yes |
| 3 | — |
747.613(b) - Required Immunizations Records, Exceptions, and Exemptions Current One child was missing an updated immunization record. |
— |
| 4 | — |
747.5005(1) - Fire Drill Monthly - Exit in 3 Minutes Fire drills were not being conducted and documented for the months of April 2023 to December 2023. This was corrected when a fire drill was conducted during the inspection and documented. |
Yes |
| 4 | — |
747.5007 - Emergency Evacuation and Relocation Diagram- Must Be On File I did not observe emergency evacuation and relocation diagram available for review. |
— |
| 3 | — |
747.801(7) - Records Maintained and Made Available - Safety Drills Documentation I did not observe documentation to show fire drills completed and smoke/ carbone monoxide detector tested for November and December 2025. |
— |
| 5 | — |
747.5115 - Smoke Detectors Testing Testing of the smoke detectors have not been conducted since March of 2023. This was corrected when the smoke detector was tested during the inspection and documented. |
Yes |
| 3 | — |
747.613(b) - Required Immunizations Records, Exceptions, and Exemptions Current One child was missing an updated immunization record. |
— |
| 4 | — |
747.5107(a) - Inspect Fire Extinguishers Monthly There is no documentation of a monthly fire extinguisher inspection being conducted since March 2023. This was corrected when the fire extinguisher was inspected by the caregiver and documented. |
Yes |
| 3 | — |
747.801(7) - Records Maintained and Made Available - Safety Drills Documentation I did not observe documentation to show fire drills completed and smoke/ carbone monoxide detector tested for November and December 2025. |
— |
| 4 | — |
747.5005(1) - Fire Drill Monthly - Exit in 3 Minutes Fire drills were not being conducted and documented for the months of April 2023 to December 2023. This was corrected when a fire drill was conducted during the inspection and documented. |
Yes |
| 4 | — |
747.5007 - Emergency Evacuation and Relocation Diagram- Must Be On File I did not observe emergency evacuation and relocation diagram available for review. |
— |
| 4 | — |
747.5337(a)(2) - Electric or Battery Operated CO System-Test Monthly The carbon monoxide detector had not been tested monthly and documented since March 2023. This was corrected when the carbon monoxide detector was tested and documented. |
Yes |
24 inspection record(s) on file from TX-HHSC.