Building Blocks Academy Cypress

Child care center · 17800 WEST RD, Houston, TX 77095-5565 · License 855022

0Compliance score
Poor

Capacity 175. InfantToddlerPre-KindergartenSchool Accepts subsidy

Violation history (80)

SeverityDateStandard / narrativeCorrected
4 746.3407 - Maintenance of Building, Grounds and Equipment
The school age playground fence was not secured at the bottom and it could caused an unsafe environment.
5 746.1205(a)(4) - Supervision ensures each child?s safety, well-being, including physical proximity and auditory or visual awareness of each child?s on going activity
A child was observed wandering the hallway.
5 746.5625(a) - Electronic Child Safety Alarm - is equipped in each vehicle
The transportation vehicle did not have an alarm.
5 746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months
The operation did not have a current fire inspection available during the inspection.
4 746.5401 - Requirement of Gas Leak Inspection
The operation did not have a current gas inspection available during the inspection.
5 746.5617(a)(5) - Required Equipment in Vehicles - Fire Extinguisher
There was no fire extinguisher in the transportation vehicle.
4 746.3407 - Maintenance of Building, Grounds and Equipment
The school-age outdoor area had a pile of stacked wood by the fence that could cause an unsafe environment; The wooden bridge had uneven planks and a loose plank that caused an unsafe environment; the tree branches were hanging on top of the playground and children were swinging on them and climbing the branches and it caused a supervision issue in another area of the playground.
3 746.2421(b) - Written Feeding Instructions - Review and Update Every 30 Days
Two infants in the infant-2 room did not have updated feeding instructions.
5 746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months
The operation did not have a current fire inspection available during the inspection.
4 746.3701(1) - Safety - Electrical Outlets Covered
The outlet cover was loose from the wall in the school age classroom and caused and unsafe environment.
5 746.1205(a)(4) - Supervision ensures each child?s safety, well-being, including physical proximity and auditory or visual awareness of each child?s on going activity
A child was observed wandering the hallway.
3 746.2421(b) - Written Feeding Instructions - Review and Update Every 30 Days
Two infants in the infant-2 room did not have updated feeding instructions.
5 746.5625(a) - Electronic Child Safety Alarm - is equipped in each vehicle
The transportation vehicle did not have an alarm.
4 746.3407 - Maintenance of Building, Grounds and Equipment
The school age playground fence was not secured at the bottom and it could caused an unsafe environment.
5 746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months
The operation did not have a current fire inspection available during the inspection.
4 746.3701(1) - Safety - Electrical Outlets Covered
The outlet cover was loose from the wall in the school age classroom and caused and unsafe environment.
5 746.5617(a)(5) - Required Equipment in Vehicles - Fire Extinguisher
There was no fire extinguisher in the transportation vehicle.
4 746.5401 - Requirement of Gas Leak Inspection
The operation did not have a current gas inspection available during the inspection.
5 746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months
The operation did not have a current fire inspection available during the inspection.
4 746.3407 - Maintenance of Building, Grounds and Equipment
The school-age outdoor area had a pile of stacked wood by the fence that could cause an unsafe environment; The wooden bridge had uneven planks and a loose plank that caused an unsafe environment; the tree branches were hanging on top of the playground and children were swinging on them and climbing the branches and it caused a supervision issue in another area of the playground.
5 746.5617(a)(5) - Required Equipment in Vehicles - Fire Extinguisher
There was no fire extinguisher in the transportation vehicle.
4 746.3701(1) - Safety - Electrical Outlets Covered
The outlet cover was loose from the wall in the school age classroom and caused and unsafe environment.
4 746.5401 - Requirement of Gas Leak Inspection
The operation did not have a current gas inspection available during the inspection.
5 746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months
The operation did not have a current fire inspection available during the inspection.
3 746.2421(b) - Written Feeding Instructions - Review and Update Every 30 Days
Two infants in the infant-2 room did not have updated feeding instructions.
5 746.5625(a) - Electronic Child Safety Alarm - is equipped in each vehicle
The transportation vehicle did not have an alarm.
5 746.1205(a)(4) - Supervision ensures each child?s safety, well-being, including physical proximity and auditory or visual awareness of each child?s on going activity
A child was observed wandering the hallway.
4 746.3407 - Maintenance of Building, Grounds and Equipment
The school-age outdoor area had a pile of stacked wood by the fence that could cause an unsafe environment; The wooden bridge had uneven planks and a loose plank that caused an unsafe environment; the tree branches were hanging on top of the playground and children were swinging on them and climbing the branches and it caused a supervision issue in another area of the playground.
4 746.3407 - Maintenance of Building, Grounds and Equipment
The school age playground fence was not secured at the bottom and it could caused an unsafe environment.
5 746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months
The operation did not have a current fire inspection available during the inspection.
5 746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months
The operation did not have a current fire inspection available during the inspection.
4 746.3407 - Maintenance of Building, Grounds and Equipment
The school age playground fence was not secured at the bottom and it could caused an unsafe environment.
4 746.3407 - Maintenance of Building, Grounds and Equipment
The school-age outdoor area had a pile of stacked wood by the fence that could cause an unsafe environment; The wooden bridge had uneven planks and a loose plank that caused an unsafe environment; the tree branches were hanging on top of the playground and children were swinging on them and climbing the branches and it caused a supervision issue in another area of the playground.
4 746.3701(1) - Safety - Electrical Outlets Covered
The outlet cover was loose from the wall in the school age classroom and caused and unsafe environment.
5 746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months
The operation did not have a current fire inspection available during the inspection.
5 746.5617(a)(5) - Required Equipment in Vehicles - Fire Extinguisher
There was no fire extinguisher in the transportation vehicle.
5 746.5625(a) - Electronic Child Safety Alarm - is equipped in each vehicle
The transportation vehicle did not have an alarm.
4 746.5401 - Requirement of Gas Leak Inspection
The operation did not have a current gas inspection available during the inspection.
3 746.2421(b) - Written Feeding Instructions - Review and Update Every 30 Days
Two infants in the infant-2 room did not have updated feeding instructions.
5 746.1205(a)(4) - Supervision ensures each child?s safety, well-being, including physical proximity and auditory or visual awareness of each child?s on going activity
A child was observed wandering the hallway.
5 746.1205(a)(4) - Supervision ensures each child?s safety, well-being, including physical proximity and auditory or visual awareness of each child?s on going activity
A child was observed wandering the hallway.
4 746.3407 - Maintenance of Building, Grounds and Equipment
The school-age outdoor area had a pile of stacked wood by the fence that could cause an unsafe environment; The wooden bridge had uneven planks and a loose plank that caused an unsafe environment; the tree branches were hanging on top of the playground and children were swinging on them and climbing the branches and it caused a supervision issue in another area of the playground.
3 746.2421(b) - Written Feeding Instructions - Review and Update Every 30 Days
Two infants in the infant-2 room did not have updated feeding instructions.
4 746.3701(1) - Safety - Electrical Outlets Covered
The outlet cover was loose from the wall in the school age classroom and caused and unsafe environment.
4 746.3407 - Maintenance of Building, Grounds and Equipment
The school age playground fence was not secured at the bottom and it could caused an unsafe environment.
5 746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months
The operation did not have a current fire inspection available during the inspection.
5 746.5617(a)(5) - Required Equipment in Vehicles - Fire Extinguisher
There was no fire extinguisher in the transportation vehicle.
5 746.5625(a) - Electronic Child Safety Alarm - is equipped in each vehicle
The transportation vehicle did not have an alarm.
4 746.5401 - Requirement of Gas Leak Inspection
The operation did not have a current gas inspection available during the inspection.
5 746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months
The operation did not have a current fire inspection available during the inspection.
5 746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months
The operation did not have a current fire inspection available during the inspection.
3 746.2421(b) - Written Feeding Instructions - Review and Update Every 30 Days
Two infants in the infant-2 room did not have updated feeding instructions.
4 746.5401 - Requirement of Gas Leak Inspection
The operation did not have a current gas inspection available during the inspection.
5 746.5617(a)(5) - Required Equipment in Vehicles - Fire Extinguisher
There was no fire extinguisher in the transportation vehicle.
4 746.3407 - Maintenance of Building, Grounds and Equipment
The school-age outdoor area had a pile of stacked wood by the fence that could cause an unsafe environment; The wooden bridge had uneven planks and a loose plank that caused an unsafe environment; the tree branches were hanging on top of the playground and children were swinging on them and climbing the branches and it caused a supervision issue in another area of the playground.
5 746.1205(a)(4) - Supervision ensures each child?s safety, well-being, including physical proximity and auditory or visual awareness of each child?s on going activity
A child was observed wandering the hallway.
5 746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months
The operation did not have a current fire inspection available during the inspection.
4 746.3701(1) - Safety - Electrical Outlets Covered
The outlet cover was loose from the wall in the school age classroom and caused and unsafe environment.
5 746.5625(a) - Electronic Child Safety Alarm - is equipped in each vehicle
The transportation vehicle did not have an alarm.
4 746.3407 - Maintenance of Building, Grounds and Equipment
The school age playground fence was not secured at the bottom and it could caused an unsafe environment.
4 746.3407 - Maintenance of Building, Grounds and Equipment
The school-age outdoor area had a pile of stacked wood by the fence that could cause an unsafe environment; The wooden bridge had uneven planks and a loose plank that caused an unsafe environment; the tree branches were hanging on top of the playground and children were swinging on them and climbing the branches and it caused a supervision issue in another area of the playground.
5 746.1205(a)(4) - Supervision ensures each child?s safety, well-being, including physical proximity and auditory or visual awareness of each child?s on going activity
A child was observed wandering the hallway.
4 746.3701(1) - Safety - Electrical Outlets Covered
The outlet cover was loose from the wall in the school age classroom and caused and unsafe environment.
5 746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months
The operation did not have a current fire inspection available during the inspection.
5 746.5625(a) - Electronic Child Safety Alarm - is equipped in each vehicle
The transportation vehicle did not have an alarm.
4 746.3407 - Maintenance of Building, Grounds and Equipment
The school age playground fence was not secured at the bottom and it could caused an unsafe environment.
3 746.2421(b) - Written Feeding Instructions - Review and Update Every 30 Days
Two infants in the infant-2 room did not have updated feeding instructions.
4 746.5401 - Requirement of Gas Leak Inspection
The operation did not have a current gas inspection available during the inspection.
5 746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months
The operation did not have a current fire inspection available during the inspection.
5 746.5617(a)(5) - Required Equipment in Vehicles - Fire Extinguisher
There was no fire extinguisher in the transportation vehicle.
4 746.3407 - Maintenance of Building, Grounds and Equipment
The school age playground fence was not secured at the bottom and it could caused an unsafe environment.
5 746.1205(a)(4) - Supervision ensures each child?s safety, well-being, including physical proximity and auditory or visual awareness of each child?s on going activity
A child was observed wandering the hallway.
5 746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months
The operation did not have a current fire inspection available during the inspection.
4 746.3701(1) - Safety - Electrical Outlets Covered
The outlet cover was loose from the wall in the school age classroom and caused and unsafe environment.
4 746.5401 - Requirement of Gas Leak Inspection
The operation did not have a current gas inspection available during the inspection.
5 746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months
The operation did not have a current fire inspection available during the inspection.
3 746.2421(b) - Written Feeding Instructions - Review and Update Every 30 Days
Two infants in the infant-2 room did not have updated feeding instructions.
5 746.5617(a)(5) - Required Equipment in Vehicles - Fire Extinguisher
There was no fire extinguisher in the transportation vehicle.
5 746.5625(a) - Electronic Child Safety Alarm - is equipped in each vehicle
The transportation vehicle did not have an alarm.
4 746.3407 - Maintenance of Building, Grounds and Equipment
The school-age outdoor area had a pile of stacked wood by the fence that could cause an unsafe environment; The wooden bridge had uneven planks and a loose plank that caused an unsafe environment; the tree branches were hanging on top of the playground and children were swinging on them and climbing the branches and it caused a supervision issue in another area of the playground.

Severity 5 = most serious. Source: official state record.

Inspections (32)

32 inspection record(s) on file from TX-HHSC.

Nearby alternatives

FacilityScoreCityDistance
Catholic Charities Of The Archdiocese Of Galveston -Houston 0 Houston
Spring Branch Presbyterian Academy 0 Houston
Wonderland Private School 0 Houston
Trotter YMCA Child Care Center 0 Houston
School of the Woods #1 0 Houston
Terrace Weekday Programs 0 Houston

Licensed facilities near this one, highest compliance score first.

Get violation alerts for this daycare

We'll email you when a new inspection or violation is posted. Free.