Capacity 100. InfantToddlerPre-KindergartenSchool
Accepts subsidy
| Severity | Date | Standard / narrative | Corrected |
|---|
| 3 | — |
746.5205(4) - Documentation of Drills It was found during the inspection that the last fire drill was documented 5/15/2025. |
— |
| 5 | — |
746.5319 - Smoke Detectors Testing It was found during the inspection that the last date the smoke detectors were tested was documented 5/20/2025. This was corrected during the inspection when staff veriifed all smoke detectors were working. |
Yes |
| 3 | — |
746.1309(a) - Documented Annual Training Area - 24 Hours Required 3 out of 4 staff files reviewed did not have verification of the annual 24 training hours. |
— |
| 4 | — |
746.5537(a)(3) - Electronic or Battery-Operated Carbon Monoxide Detector-Document Test Date, Battery Installation Date, and Staff Name Testing and Installation It was found during the inspection that the operation documented the last time they checked the Carbon Monoxide Detector was in July 2023. This was corrected during the inspection. |
Yes |
| 5 | — |
746.1203(2) - Responsibilities of Caregivers - Know Group Responsible For There was a caregiver in the naproom that did not know the number of children that they were responsible for. |
— |
| 4 | — |
746.3819 - Food Allergy Emergency Plan Signed by Parents and Health Care Professional 1 out of 1 records reviewed for Food Allergies did not have a Food Allergy plan on file. |
— |
| 4 | — |
746.5205(1) - Fire Drill Monthly - Exit in 3 Minutes It was found during the inspection the operation has not conducted a fire drill since July 2023. |
— |
| 5 | — |
746.2426 - Infant May Not Sleep in a Restrictive Device During the inspection, there was 9 month old child asleep in a restive device in the infant classroom. CI: This was corrected at the inspection as the child was removed from the restive device and placed in there crib. |
Yes |
| 3 | — |
746.4003(a)(8) - First Aid Kit Incomplete - Tweezers A first aid kit was observed to be missing tweezers. This was corrected during the inspection when staff placed tweezers in the first aid kit. |
— |
| 5 | — |
746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months During the inspection, it was found that the most recent fire inspection report was dated 10/24/2023. |
— |
| 4 | — |
746.1301(a)(2)(A) - Training Requirements for Employees, Caregivers, and Directors - Pre-Service Training 1 out of 4 staff files reviewed did not have verification of preservice training. |
— |
| 3 | — |
746.5205(4) - Documentation of Drills It was found during the inspection that the last fire drill was documented 4/16/2026 |
— |
| 3 | — |
746.801(13) - Required Records Maintained and Made Available - Gas Inspection Report During the inspection it was observed that the last gas inspection was last conducted on 2/01/2024. |
— |
| 5 | — |
746.2415(b) - AP Cribs - Only Snug Fitting Sheet and Crib Mattress Cover Allowed if Infant Younger than 12 Months of Age During the inspection, there was a 9 month old asleep in there crib wrapped up in a blanket with a pillow. CI: This was corrected at the inspection as the items were removed from the crib. |
Yes |
| 5 | — |
746.5319 - Smoke Detectors Testing It was found during the inspection that the operation has not documented checking the smoke detectors since July 2023. This was corrected during the inspection. |
Yes |
| 3 | — |
746.901 - Required Personnel Records 1 out of 4 staff files reviewed did not have verification of education qualification, Form 2985, Form 2912, review verification of orientation and the operations personnel and operational policies. |
— |
| 3 | — |
746.4135(b) - Children's Products- Annual Certification The last annual certification was conducted on 9/7/2022. |
— |
| 5 | — |
746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months It was found during the inspection that the operation last fire inspection was conducted on 4/13/2022 therefore it has been over 12 months since their last annual fire inspection. |
— |
| 4 | — |
746.5307(a) - Inspect Fire Extinguishers Monthly It was found during the inspection that they had not documented dates this has been checked since July 2023. This was corrected during the inspection. |
Yes |
| 3 | — |
746.5205(4) - Documentation of Drills It was found during the inspection that the last fire drill was documented 4/16/2026 |
— |
| 3 | — |
746.901 - Required Personnel Records 1 out of 4 staff files reviewed did not have verification of education qualification, Form 2985, Form 2912, review verification of orientation and the operations personnel and operational policies. |
— |
| 4 | — |
746.1301(a)(2)(A) - Training Requirements for Employees, Caregivers, and Directors - Pre-Service Training 1 out of 4 staff files reviewed did not have verification of preservice training. |
— |
| 3 | — |
746.4135(b) - Children's Products- Annual Certification The last annual certification was conducted on 9/7/2022. |
— |
| 3 | — |
746.1309(a) - Documented Annual Training Area - 24 Hours Required 3 out of 4 staff files reviewed did not have verification of the annual 24 training hours. |
— |
| 4 | — |
746.5205(1) - Fire Drill Monthly - Exit in 3 Minutes It was found during the inspection the operation has not conducted a fire drill since July 2023. |
— |
| 5 | — |
746.2426 - Infant May Not Sleep in a Restrictive Device During the inspection, there was 9 month old child asleep in a restive device in the infant classroom. CI: This was corrected at the inspection as the child was removed from the restive device and placed in there crib. |
Yes |
| 3 | — |
746.4003(a)(8) - First Aid Kit Incomplete - Tweezers A first aid kit was observed to be missing tweezers. This was corrected during the inspection when staff placed tweezers in the first aid kit. |
— |
| 5 | — |
746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months During the inspection, it was found that the most recent fire inspection report was dated 10/24/2023. |
— |
| 5 | — |
746.2415(b) - AP Cribs - Only Snug Fitting Sheet and Crib Mattress Cover Allowed if Infant Younger than 12 Months of Age During the inspection, there was a 9 month old asleep in there crib wrapped up in a blanket with a pillow. CI: This was corrected at the inspection as the items were removed from the crib. |
Yes |
| 4 | — |
746.5537(a)(3) - Electronic or Battery-Operated Carbon Monoxide Detector-Document Test Date, Battery Installation Date, and Staff Name Testing and Installation It was found during the inspection that the operation documented the last time they checked the Carbon Monoxide Detector was in July 2023. This was corrected during the inspection. |
Yes |
| 5 | — |
746.5319 - Smoke Detectors Testing It was found during the inspection that the last date the smoke detectors were tested was documented 5/20/2025. This was corrected during the inspection when staff veriifed all smoke detectors were working. |
Yes |
| 4 | — |
746.5307(a) - Inspect Fire Extinguishers Monthly It was found during the inspection that they had not documented dates this has been checked since July 2023. This was corrected during the inspection. |
Yes |
| 5 | — |
746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months It was found during the inspection that the operation last fire inspection was conducted on 4/13/2022 therefore it has been over 12 months since their last annual fire inspection. |
— |
| 3 | — |
746.5205(4) - Documentation of Drills It was found during the inspection that the last fire drill was documented 5/15/2025. |
— |
| 5 | — |
746.5319 - Smoke Detectors Testing It was found during the inspection that the operation has not documented checking the smoke detectors since July 2023. This was corrected during the inspection. |
Yes |
| 5 | — |
746.1203(2) - Responsibilities of Caregivers - Know Group Responsible For There was a caregiver in the naproom that did not know the number of children that they were responsible for. |
— |
| 4 | — |
746.3819 - Food Allergy Emergency Plan Signed by Parents and Health Care Professional 1 out of 1 records reviewed for Food Allergies did not have a Food Allergy plan on file. |
— |
| 3 | — |
746.801(13) - Required Records Maintained and Made Available - Gas Inspection Report During the inspection it was observed that the last gas inspection was last conducted on 2/01/2024. |
— |
| 3 | — |
746.801(13) - Required Records Maintained and Made Available - Gas Inspection Report During the inspection it was observed that the last gas inspection was last conducted on 2/01/2024. |
— |
| 5 | — |
746.2426 - Infant May Not Sleep in a Restrictive Device During the inspection, there was 9 month old child asleep in a restive device in the infant classroom. CI: This was corrected at the inspection as the child was removed from the restive device and placed in there crib. |
Yes |
| 3 | — |
746.5205(4) - Documentation of Drills It was found during the inspection that the last fire drill was documented 4/16/2026 |
— |
| 5 | — |
746.2415(b) - AP Cribs - Only Snug Fitting Sheet and Crib Mattress Cover Allowed if Infant Younger than 12 Months of Age During the inspection, there was a 9 month old asleep in there crib wrapped up in a blanket with a pillow. CI: This was corrected at the inspection as the items were removed from the crib. |
Yes |
| 4 | — |
746.3819 - Food Allergy Emergency Plan Signed by Parents and Health Care Professional 1 out of 1 records reviewed for Food Allergies did not have a Food Allergy plan on file. |
— |
| 3 | — |
746.5205(4) - Documentation of Drills It was found during the inspection that the last fire drill was documented 5/15/2025. |
— |
| 5 | — |
746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months During the inspection, it was found that the most recent fire inspection report was dated 10/24/2023. |
— |
| 4 | — |
746.5205(1) - Fire Drill Monthly - Exit in 3 Minutes It was found during the inspection the operation has not conducted a fire drill since July 2023. |
— |
| 4 | — |
746.5307(a) - Inspect Fire Extinguishers Monthly It was found during the inspection that they had not documented dates this has been checked since July 2023. This was corrected during the inspection. |
Yes |
| 3 | — |
746.1309(a) - Documented Annual Training Area - 24 Hours Required 3 out of 4 staff files reviewed did not have verification of the annual 24 training hours. |
— |
| 3 | — |
746.4135(b) - Children's Products- Annual Certification The last annual certification was conducted on 9/7/2022. |
— |
| 5 | — |
746.5319 - Smoke Detectors Testing It was found during the inspection that the operation has not documented checking the smoke detectors since July 2023. This was corrected during the inspection. |
Yes |
| 4 | — |
746.5537(a)(3) - Electronic or Battery-Operated Carbon Monoxide Detector-Document Test Date, Battery Installation Date, and Staff Name Testing and Installation It was found during the inspection that the operation documented the last time they checked the Carbon Monoxide Detector was in July 2023. This was corrected during the inspection. |
Yes |
| 3 | — |
746.4003(a)(8) - First Aid Kit Incomplete - Tweezers A first aid kit was observed to be missing tweezers. This was corrected during the inspection when staff placed tweezers in the first aid kit. |
— |
| 3 | — |
746.901 - Required Personnel Records 1 out of 4 staff files reviewed did not have verification of education qualification, Form 2985, Form 2912, review verification of orientation and the operations personnel and operational policies. |
— |
| 5 | — |
746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months It was found during the inspection that the operation last fire inspection was conducted on 4/13/2022 therefore it has been over 12 months since their last annual fire inspection. |
— |
| 5 | — |
746.1203(2) - Responsibilities of Caregivers - Know Group Responsible For There was a caregiver in the naproom that did not know the number of children that they were responsible for. |
— |
| 5 | — |
746.5319 - Smoke Detectors Testing It was found during the inspection that the last date the smoke detectors were tested was documented 5/20/2025. This was corrected during the inspection when staff veriifed all smoke detectors were working. |
Yes |
| 4 | — |
746.1301(a)(2)(A) - Training Requirements for Employees, Caregivers, and Directors - Pre-Service Training 1 out of 4 staff files reviewed did not have verification of preservice training. |
— |
| 3 | — |
746.901 - Required Personnel Records 1 out of 4 staff files reviewed did not have verification of education qualification, Form 2985, Form 2912, review verification of orientation and the operations personnel and operational policies. |
— |
| 3 | — |
746.5205(4) - Documentation of Drills It was found during the inspection that the last fire drill was documented 4/16/2026 |
— |
| 3 | — |
746.801(13) - Required Records Maintained and Made Available - Gas Inspection Report During the inspection it was observed that the last gas inspection was last conducted on 2/01/2024. |
— |
| 4 | — |
746.3819 - Food Allergy Emergency Plan Signed by Parents and Health Care Professional 1 out of 1 records reviewed for Food Allergies did not have a Food Allergy plan on file. |
— |
| 5 | — |
746.2426 - Infant May Not Sleep in a Restrictive Device During the inspection, there was 9 month old child asleep in a restive device in the infant classroom. CI: This was corrected at the inspection as the child was removed from the restive device and placed in there crib. |
Yes |
| 5 | — |
746.2415(b) - AP Cribs - Only Snug Fitting Sheet and Crib Mattress Cover Allowed if Infant Younger than 12 Months of Age During the inspection, there was a 9 month old asleep in there crib wrapped up in a blanket with a pillow. CI: This was corrected at the inspection as the items were removed from the crib. |
Yes |
| 4 | — |
746.5537(a)(3) - Electronic or Battery-Operated Carbon Monoxide Detector-Document Test Date, Battery Installation Date, and Staff Name Testing and Installation It was found during the inspection that the operation documented the last time they checked the Carbon Monoxide Detector was in July 2023. This was corrected during the inspection. |
Yes |
| 5 | — |
746.5319 - Smoke Detectors Testing It was found during the inspection that the operation has not documented checking the smoke detectors since July 2023. This was corrected during the inspection. |
Yes |
| 4 | — |
746.5205(1) - Fire Drill Monthly - Exit in 3 Minutes It was found during the inspection the operation has not conducted a fire drill since July 2023. |
— |
| 5 | — |
746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months It was found during the inspection that the operation last fire inspection was conducted on 4/13/2022 therefore it has been over 12 months since their last annual fire inspection. |
— |
| 3 | — |
746.4135(b) - Children's Products- Annual Certification The last annual certification was conducted on 9/7/2022. |
— |
| 3 | — |
746.1309(a) - Documented Annual Training Area - 24 Hours Required 3 out of 4 staff files reviewed did not have verification of the annual 24 training hours. |
— |
| 4 | — |
746.5307(a) - Inspect Fire Extinguishers Monthly It was found during the inspection that they had not documented dates this has been checked since July 2023. This was corrected during the inspection. |
Yes |
| 4 | — |
746.1301(a)(2)(A) - Training Requirements for Employees, Caregivers, and Directors - Pre-Service Training 1 out of 4 staff files reviewed did not have verification of preservice training. |
— |
| 5 | — |
746.1203(2) - Responsibilities of Caregivers - Know Group Responsible For There was a caregiver in the naproom that did not know the number of children that they were responsible for. |
— |
| 3 | — |
746.5205(4) - Documentation of Drills It was found during the inspection that the last fire drill was documented 5/15/2025. |
— |
| 3 | — |
746.4003(a)(8) - First Aid Kit Incomplete - Tweezers A first aid kit was observed to be missing tweezers. This was corrected during the inspection when staff placed tweezers in the first aid kit. |
— |
| 5 | — |
746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months During the inspection, it was found that the most recent fire inspection report was dated 10/24/2023. |
— |
| 5 | — |
746.5319 - Smoke Detectors Testing It was found during the inspection that the last date the smoke detectors were tested was documented 5/20/2025. This was corrected during the inspection when staff veriifed all smoke detectors were working. |
Yes |
| 3 | — |
746.5205(4) - Documentation of Drills It was found during the inspection that the last fire drill was documented 4/16/2026 |
— |
| 3 | — |
746.4135(b) - Children's Products- Annual Certification The last annual certification was conducted on 9/7/2022. |
— |
| 4 | — |
746.5205(1) - Fire Drill Monthly - Exit in 3 Minutes It was found during the inspection the operation has not conducted a fire drill since July 2023. |
— |
| 4 | — |
746.5307(a) - Inspect Fire Extinguishers Monthly It was found during the inspection that they had not documented dates this has been checked since July 2023. This was corrected during the inspection. |
Yes |
| 3 | — |
746.1309(a) - Documented Annual Training Area - 24 Hours Required 3 out of 4 staff files reviewed did not have verification of the annual 24 training hours. |
— |
| 3 | — |
746.4003(a)(8) - First Aid Kit Incomplete - Tweezers A first aid kit was observed to be missing tweezers. This was corrected during the inspection when staff placed tweezers in the first aid kit. |
— |
| 5 | — |
746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months During the inspection, it was found that the most recent fire inspection report was dated 10/24/2023. |
— |
| 5 | — |
746.5101(a) - Annual Fire Inspection - Before Initial Permit Issued and Every 12 Months It was found during the inspection that the operation last fire inspection was conducted on 4/13/2022 therefore it has been over 12 months since their last annual fire inspection. |
— |
| 4 | — |
746.1301(a)(2)(A) - Training Requirements for Employees, Caregivers, and Directors - Pre-Service Training 1 out of 4 staff files reviewed did not have verification of preservice training. |
— |
| 5 | — |
746.1203(2) - Responsibilities of Caregivers - Know Group Responsible For There was a caregiver in the naproom that did not know the number of children that they were responsible for. |
— |
| 5 | — |
746.5319 - Smoke Detectors Testing It was found during the inspection that the last date the smoke detectors were tested was documented 5/20/2025. This was corrected during the inspection when staff veriifed all smoke detectors were working. |
Yes |
| 4 | — |
746.5537(a)(3) - Electronic or Battery-Operated Carbon Monoxide Detector-Document Test Date, Battery Installation Date, and Staff Name Testing and Installation It was found during the inspection that the operation documented the last time they checked the Carbon Monoxide Detector was in July 2023. This was corrected during the inspection. |
Yes |
| 3 | — |
746.801(13) - Required Records Maintained and Made Available - Gas Inspection Report During the inspection it was observed that the last gas inspection was last conducted on 2/01/2024. |
— |
| 5 | — |
746.5319 - Smoke Detectors Testing It was found during the inspection that the operation has not documented checking the smoke detectors since July 2023. This was corrected during the inspection. |
Yes |
| 4 | — |
746.3819 - Food Allergy Emergency Plan Signed by Parents and Health Care Professional 1 out of 1 records reviewed for Food Allergies did not have a Food Allergy plan on file. |
— |
| 3 | — |
746.5205(4) - Documentation of Drills It was found during the inspection that the last fire drill was documented 5/15/2025. |
— |
| 3 | — |
746.901 - Required Personnel Records 1 out of 4 staff files reviewed did not have verification of education qualification, Form 2985, Form 2912, review verification of orientation and the operations personnel and operational policies. |
— |
| 5 | — |
746.2415(b) - AP Cribs - Only Snug Fitting Sheet and Crib Mattress Cover Allowed if Infant Younger than 12 Months of Age During the inspection, there was a 9 month old asleep in there crib wrapped up in a blanket with a pillow. CI: This was corrected at the inspection as the items were removed from the crib. |
Yes |
| 5 | — |
746.2426 - Infant May Not Sleep in a Restrictive Device During the inspection, there was 9 month old child asleep in a restive device in the infant classroom. CI: This was corrected at the inspection as the child was removed from the restive device and placed in there crib. |
Yes |
| 3 | — |
746.901 - Required Personnel Records 1 out of 4 staff files reviewed did not have verification of education qualification, Form 2985, Form 2912, review verification of orientation and the operations personnel and operational policies. |
— |
| 4 | — |
746.5537(a)(3) - Electronic or Battery-Operated Carbon Monoxide Detector-Document Test Date, Battery Installation Date, and Staff Name Testing and Installation It was found during the inspection that the operation documented the last time they checked the Carbon Monoxide Detector was in July 2023. This was corrected during the inspection. |
Yes |
| 5 | — |
746.1203(2) - Responsibilities of Caregivers - Know Group Responsible For There was a caregiver in the naproom that did not know the number of children that they were responsible for. |
— |
| 5 | — |
746.5319 - Smoke Detectors Testing It was found during the inspection that the operation has not documented checking the smoke detectors since July 2023. This was corrected during the inspection. |
Yes |
| 3 | — |
746.1309(a) - Documented Annual Training Area - 24 Hours Required 3 out of 4 staff files reviewed did not have verification of the annual 24 training hours. |
— |